1066540000/01/12.11

TC Input, Cold Junction Compensation (CJC)

CJC: external with ACT20X-CJC-HTI
(1160640000)

+20…+28 °C ≤

1 °C

-20…+20 °C and +28…+60 °C ≤

1.6 °C

CJC via internal sensor

t = internal temperature – ambient temperature

(2.0 °C + 0.4 °C * t)

Sensor error detection (programmable, only wire
breakage)

ON/OFF

Sensor error current:

when detecting
else


nom. 2 μA
0 μA

Current Input

Measurement range

0…20 mA

Programmable measurement ranges

0…20 and 4…20 mA

Input resistance

nom. 20 Ω + PTC 50 Ω

Sensor error detection:

loop break (only when input is selected as
4…20 mA)


Yes

Voltage Input

Measurement range

0…12 V DC

Programmable measurement ranges

0…1 V / 0.2…1 V / 0…5 V / 1…5 V / 0…10 V /
2…10 V

Input resistance

nom. > 10 MΩ

Current Output

Signal range (span)

0…23 mA

Programmable signal ranges

0…20 mA / 4…20 mA / 20…0 mA / 20…4 mA

Load max.

4 mA / 600 Ω / 12 V DC

Load stability

≤ 0.01 % of span / 100 Ω

Sensor error detection

0 / 3.5 mA / 23 mA / none

NAMUR NE 43, Upscale / Downscale

23 mA / 3.5 mA

Output limitation:

on 4…20 and 20…4 mA signals
on 0…20 and 20…0 mA signals


3.8…20.5 mA
0…20.5 mA

Current limit

≤ 28 mA