3 electrical connections, 4 specifications, Features – Weidmuller ACT20X User Manual

Page 56: Electrical connections, Specifications

Advertising
background image

Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater)

56

1066540000/01/12.11

7.5.3 Electrical

Connections

Terminal

Function

Connector

Terminal

Function

Connector

11 I

Passive

 41

Out

12

I Passive +

42

Out +

output

channel 1

13

I Active Return

43

Out

14

I Active Supply

Ex input

channel 1

44 Out

+

output

channel 2

21 I

Passive

 51

GND

22

I Passive +

52

+24 V DC

power supply

23

I Active Return

53

NC

24

I Active Supply

Ex input

channel 2

54 COM

status relay

Table 7-10: Electrical Connections


7.5.4 Specifications

Features
 HART-compatible for 0.5...2.5 kHz
 Configuration and monitoring via FDT/DTM-Software "WI-Manager".
 The device can be mounted in the safe area and in Zone 2 / Division 2 and receive signals from Zone 0, 1,

2, 20, 21 and 22, as well as Class I/II/III, Division 1, Group A-G.

 The active or passive mA current signal inputs are completely electrically isolated.
 The device detects automatically whether an active or passive current signal is connected.
 The two-channel device can be used as a signal splitter.
 Extended self diagnostic: Monitoring of error events (e.g. cable breakage) via status relay.
 Front LEDs indicates operation status and malfunction.
 3-way galvanic isolation between input, output and power supply.

Advertising