Power supply input signals output signals – Weidmuller ACT20X User Manual

Page 25

Advertising
background image

Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator)

1066540000/01/12.11

25

Ch

a

n

n

e

l 1

:

Ch

a

n

n

e

l 2

:

Zone 0, 1, 2, 20, 21, 22 /
Cl. I/II/II I, div. 1 gr. A-G

Zone 2 / FM Cl. I
div. 2, gr. A-D or safe area

Power Supply

Input Signals

Output Signals

44

43

42

41

24

23

22

21

14

13

12

11

51

52

53

54

Opto +

Opto -

Opto -

Opto +

Relay

Relay

Relay

Channel 1:

N.O. or

N.C.

Relay

Channel 2:

N.O. or

N.C.

Ch. 2:

Ch. 1:

NAMUR

+

-

Rp

Rs

Rp

Mechanical

switch

Module status

Module status

Gnd. -

Supply +19.2...31.2 VDC

N.C.

NAMUR

+

-

Rp

Rs

Rp

Mechanical

switch

Illustration 7-3: Applications

Input NAMUR / Mechanical Switch with Series and Parallel Resistance

NAMUR sensor, according to

EN 60947-5-6

Mechanical Switch, Series resistance (R

S

) nom.

750

Mechanical Switch, Parallel resistance (R

P

)

nom. 15 kΩ

Frequency range

0…5 kHz

Min. pulse length

> 0.1 ms

Resistance

nom. 1 kΩ

Trigger level, signal

< 1.2 mA, > 2.1 mA

Trigger level, cable fault

< 0.1 mA, > 6.5 mA