Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator)
26
1066540000/01/12.11
Status Relay
Safe Area
Zone 2 Installation
Voltage max.
125 V AC / 110 V
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Relay Output
Safe Area
Zone 2 Installation
Voltage max.
250 V AC / 30 V
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
16 VA / 60 W
Max. switching frequency
20 Hz
Opto NPN Output
Max. switching frequency
5 kHz
Min. pulse length
60 μs
Max. load, current / voltage
80 mA / 30 V DC
Voltage drop at 80 mA
< 2.5 V DC
Power Supply
Supply voltage
19.2…31.2 V DC
NAMUR supply
8 V DC / 8 mA
Max. consumption (2-channels)
≤ 3 W
Fuse
400 mA / 250 V AC
Isolation Voltages (reinforced insulation), Test/Operation
Inputs / outputs / supply
2.6 kV AC / 300 V AC
Output 1 to output 2
1.5 kV AC / 150 V AC
Status relay to supply
1.5 kV AC / 150 V AC
Environmental Specifications
Specifications range
-20…+60 °C
Storage temperature
-20…+85 °C
Relative humidity (non-condensation)
< 95 %
Calibration temperature
+20…28 °C