Weidmuller ACT20X User Manual

Page 26

Advertising
background image

Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator)

26

1066540000/01/12.11

Status Relay

Safe Area

Zone 2 Installation

Voltage max.

125 V AC / 110 V

32 V AC / 32 V DC

Current max.

0.5 A AC / 0.3 A

0.5 A AC / 1 A DC

Power max.

62.5 VA / 32 W

16 VA / 32 W

Relay Output

Safe Area

Zone 2 Installation

Voltage max.

250 V AC / 30 V

32 V AC / 30 V DC

Current max.

2 A AC / 2 A DC

2 A AC / 2 A DC

Power max.

500 VA / 60 W

16 VA / 60 W

Max. switching frequency

20 Hz

Opto NPN Output

Max. switching frequency

5 kHz

Min. pulse length

60 μs

Max. load, current / voltage

80 mA / 30 V DC

Voltage drop at 80 mA

< 2.5 V DC

Power Supply

Supply voltage

19.2…31.2 V DC

NAMUR supply

8 V DC / 8 mA

Max. consumption (2-channels)

≤ 3 W

Fuse

400 mA / 250 V AC

Isolation Voltages (reinforced insulation), Test/Operation

Inputs / outputs / supply

2.6 kV AC / 300 V AC

Output 1 to output 2

1.5 kV AC / 150 V AC

Status relay to supply

1.5 kV AC / 150 V AC

Environmental Specifications

Specifications range

-20…+60 °C

Storage temperature

-20…+85 °C

Relative humidity (non-condensation)

< 95 %

Calibration temperature

+20…28 °C