Weidmuller ACT20X User Manual
Page 171
Advertising
Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)
1066540000/01/12.11
171
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Current Input
U
m
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Advertising