Pccc object, N-files (continued), Continued) – Rockwell Automation 22-COMM-E EtherNet/IP Adapter User Manual

Page 132

Advertising
background image

C-20

EtherNet/IP Objects

N-Files (Continued)

Important: If your controller or HMI platform supports CIP messaging,

use the CIP Parameter object to get and set parameters.

PCCC Object

(Continued)

N-File

Description

N10 – N18

These N-files let you read and write parameter values in the drive and the
adapter.

Single-Drive Mode

Multi-Drive Mode

N10:0
N10:1 – 999

Number of parameters in the drive
Drive parameters 1 – 999

Number of parameters in Drive 0
Drive 0 parameters 1 - 999

N11:0 – 999

Drive parameters 1000 – 1999

Drive 0 parameters 1000 - 1999

N12:0 – 999

Drive parameters 2000 – 2999

Drive 0 parameters 2000 - 2999

N13:0

Number of parameters in this
adapter

Number of parameters in this
adapter

N13:1 – 999

Parameters 1 – 999 in this adapter

Parameters 1 – 999 in this adapter

N14:0

Number of parameters in this
adapter

Number of parameters in Drive 1

N14:1 – 999

Parameters 1 – 999 in this adapter

Drive 1 parameters 1 – 999

N15:0

Number of parameters in the slave

Number of parameters in Drive 2

N15:1 – 999

Parameters 1 – 999 in the slave

Drive 2 parameters 1 – 999

N16:0

Not supported

Number of parameters in Drive 3

N16:1 – 999

Not supported

Drive 3 parameters 1 – 999

N17:0

Not supported

Number of parameters in Drive 4

N17:1 – 999

Not supported

Drive 4 parameters 1 – 999

N18:0

Not supported

Number of parameters in this
adapter

N18:1 – 999

Not supported

Parameters 1 – 999 in this adapter

Advertising