Configuring the Scanner or Bridge

4-5

The Module Properties dialog box (

Figure 4.8

) appears.

Figure 4.8 Module Properties Dialog Box - Page 1

3. Edit the following information about the adapter:

4. Under Connection Parameters, edit the following:

Type the number of bytes that are required for your I/O in the Input
Size and Output Size boxes. The size will depend on the I/O that you
enabled in the adapter. This information can be found in Parameter
22 - [DSI I/O Cfg]
in the adapter.

Table 4.A

shows common

configuration Input/Output sizes.

In our example, we typed 4 in the Input Size and Output Size boxes
because the Operating Mode Switch on the adapter is set to “Single”
(default) and Parameter 22 - [DSI I/O Cfg] is set to “Drive 0” (only
one drive being connected). Logic Command/Reference uses 2

Box

Type

Name

A name to identify the adapter and drive.

Comm. Format

Data - INT.
This setting formats the data in 16-bit words.

IP Address

The IP address of the adapter.

Box

Assembly Instance Size

Input

1 (This value is
required.)

The value will vary based on your application
(setting of Parameter 22 - [DSI I/O Cfg]). It
will contain 2 additional words for ENBT
overhead. Refer to

Table 4.A

on

page 4-6

.

Output

2 (This value is
required.)

The value will vary based on your application
(setting of Parameter 22 - [DSI I/O Cfg]).
Refer to

Table 4.A

on

page 4-6

.

Configuration 6 (This value is

required.)

0 (This value is required.)