Rockwell Automation 22-COMM-E EtherNet/IP Adapter User Manual
Page 29

Configuring the Adapter
3-5
By default, the adapter is configured so that you set its IP address, subnet
mask, and gateway address using a BOOTP server. If you want to set
these functions using the adapter’s parameters instead, you must first
disable BOOTP and then set the appropriate parameters in the adapter.
To disable the BOOTP feature
1. Set the value of Parameter 02 - [BOOTP] to Disabled.
Figure 3.4 Example BOOTP Screen on PowerFlex 4-Class HIM (22-HIM-*)
2. Reset the adapter. See
Resetting the Adapter
section in this chapter.
After disabling the BOOTP feature, you can then configure the IP
address, subnet mask, and gateway using the adapter’s parameters.
To set an IP address using parameters
1. Verify that Parameter 02 - [BOOTP] is set to Disabled. This
parameter must be set to Disabled in order to configure the IP
address using parameters.
2. Set the value of Parameters 03 - [IP Addr Cfg 1] through 06 - [IP
Addr Cfg 4] to a unique IP address.
Figure 3.5 Example IP Address Screen on PowerFlex 4-Class HIM (22-HIM-*)
Setting the IP Address, Subnet Mask, and Gateway
Address
Value Setting
0
Disabled
1
Enabled (Default)
BOOTP
Parameter:
#
002
0
VALUE
LIMITS
SEL
X
Default = 0.0.0.0
255 . 255 . 255 . 255
[IP Addr Cfg 1]
[IP Addr Cfg 2]
[IP Addr Cfg 3]
[IP Addr Cfg 4]
IP Addr Cfg 1
Parameter:
#
003
0
VALUE
LIMITS
SEL
X