Controllogix example, Drive settings for the example program – Rockwell Automation 22-COMM-E EtherNet/IP Adapter User Manual

Page 67

Advertising
background image

Using Multi-Drive Mode

7-7

Drive Settings for the Example Program

The following common Tags are used:

The following Tags are used for Drive 0:

Parameter

Value

Drive 0 Drive 1 Drive 2 Drive 3 Drive 4

P36 - [Start Source]

5

5

5

5

5

P38 - [Speed Reference]

5

5

5

5

5

A103 - [Comm Data Rate]

4

4

4

4

4

A104 - [Comm Node Addr]

(1)

(1)

The settings for these parameters must match the respective parameter
settings in the adapter (Parameter 17 - [Drv 0 Addr] through Parameter 21
- [Drv 4 Addr]).

1

2

3

4

5

A105 - [Comm Loss Action]

0

0

0

0

0

A106 - [Comm Loss Time]

5

5

5

5

5

A107 - [Comm Format]

0

0

0

0

0

ControlLogix Example

Tag Name

Type

Description

MultiDrive_Demo : I

AB: 1756_E...

1756-ENBT I/O

MultiDrive_Demo : O

AB: 1756_E...

MultiDrive_Demo : C

AB: 1756_E...

Drive Input Image

INT [10]

Input Image Table

Drive Output Image

INT [10]

Output Image Table

Tag Name

Type

Description

Drive 0 Command Stop

BOOL

Logic Command bit 0 (STOP)

Drive 0 Command Start

BOOL

Logic Command bit 1 (START)

Drive 0 Command Jog

BOOL

Logic Command bit 2 (JOG)

Drive 0 Command Clear Faults BOOL

Logic Command bit 3 (CLEAR FAULTS)

Drive 0 Command Forward

BOOL

Logic Command bit 4 (FORWARD)

Drive 0 Reference

INT

Speed Reference

Drive 0 Status Ready

BOOL

Logic Status bit 0 (READY)

Drive 0 Status Active

BOOL

Logic Status bit 1 (ACTIVE)

Drive 0 Status Forward

BOOL

Logic Status bit 3 (FORWARD)

Drive 0 Status Faulted

BOOL

Logic Status bit 7 (FAULT)

Drive 0 Status At Reference

BOOL

Logic Status bit 8 (AT SPEED)

Drive 0 Feedback

INT

Speed Feedback

Perform Parameter Read 0

BOOL

Initiates the parameter read

Parameter RD Value 0

INT

Read value of the parameter

Parameter RD Message 0

MESSAGE Get_Attribute_Single (Read)