Rockwell Automation 22-COMM-E EtherNet/IP Adapter User Manual
Page 30

3-6
Configuring the Adapter
3. Reset the adapter. See
Resetting the Adapter
section in this chapter.
The Net A status indicator will be solid green or flashing green if the
IP address is correctly configured.
To set a subnet mask using parameters
1. Verify that Parameter 02 - [BOOTP] is set to Disabled. This
parameter must be set to Disabled in order to configure the subnet
mask using parameters.
2. Set the value of Parameters 07 - [Subnet Cfg 1] through 10 -
[Subnet Cfg 4] to the desired value for the subnet mask.
Figure 3.6 Example Subnet Mask Screen on PowerFlex 4-Class HIM (22-HIM-*)
3. Reset the adapter. See
Resetting the Adapter
section in this chapter.
To set a gateway address for the adapter using parameters
1. Verify that Parameter 02 - [BOOTP] is set to Disabled. This
parameter must be set to Disabled in order to configure the gateway
address using parameters.
2. Set the value of Parameters 11 - [Gateway Cfg 1] through 14 -
[Gateway Cfg 4] to the IP address of the gateway device.
Figure 3.7 Example Gateway Screen on PowerFlex 4-Class HIM (22-HIM-*)
3. Reset the adapter. See
Resetting the Adapter
section in this chapter.
Default = 0.0.0.0
255 . 255 . 255 . 255
[Subnet Cfg 1]
[Subnet Cfg 2]
[Subnet Cfg 3]
[Subnet Cfg 4]
Subnet Cfg 1
Parameter:
#
007
0
VALUE
LIMITS
SEL
X
Default = 0.0.0.0
255 . 255 . 255 . 255
[Gateway Cfg 1]
[Gateway Cfg 2]
[Gateway Cfg 3]
[Gateway Cfg 4]
Gateway Cfg 1
Parameter:
#
011
0
VALUE
LIMITS
SEL
X