Rockwell Automation 22-COMM-E EtherNet/IP Adapter User Manual

Page 30

Advertising
background image

3-6

Configuring the Adapter

3. Reset the adapter. See

Resetting the Adapter

section in this chapter.

The Net A status indicator will be solid green or flashing green if the
IP address is correctly configured.

To set a subnet mask using parameters

1. Verify that Parameter 02 - [BOOTP] is set to Disabled. This

parameter must be set to Disabled in order to configure the subnet
mask using parameters.

2. Set the value of Parameters 07 - [Subnet Cfg 1] through 10 -

[Subnet Cfg 4] to the desired value for the subnet mask.

Figure 3.6 Example Subnet Mask Screen on PowerFlex 4-Class HIM (22-HIM-*)

3. Reset the adapter. See

Resetting the Adapter

section in this chapter.

To set a gateway address for the adapter using parameters

1. Verify that Parameter 02 - [BOOTP] is set to Disabled. This

parameter must be set to Disabled in order to configure the gateway
address using parameters.

2. Set the value of Parameters 11 - [Gateway Cfg 1] through 14 -

[Gateway Cfg 4] to the IP address of the gateway device.

Figure 3.7 Example Gateway Screen on PowerFlex 4-Class HIM (22-HIM-*)

3. Reset the adapter. See

Resetting the Adapter

section in this chapter.

Default = 0.0.0.0

255 . 255 . 255 . 255

[Subnet Cfg 1]

[Subnet Cfg 2]

[Subnet Cfg 3]

[Subnet Cfg 4]

Subnet Cfg 1

Parameter:

#

007

0

VALUE

LIMITS

SEL

X

Default = 0.0.0.0

255 . 255 . 255 . 255

[Gateway Cfg 1]

[Gateway Cfg 2]

[Gateway Cfg 3]

[Gateway Cfg 4]

Gateway Cfg 1

Parameter:

#

011

0

VALUE

LIMITS

SEL

X

Advertising