Dpi device object, Class code, Instances – Rockwell Automation 22-COMM-E EtherNet/IP Adapter User Manual

Page 133: Class attributes

Advertising
background image

EtherNet/IP Objects

C-21

Class Code



Instances

The number of instances depends on the number of components in the
device. The total number of components can be read in Instance 0, Class
Attribute 4.

Class Attributes

DPI Device Object

Hexadecimal

Decimal

0x92

146

Instances (Dec.) Single-Drive Mode

Multi-Drive Mode

0 – 16383

Instances 0 – 16383 in the drive

Instances 0 – 16383 in Drive 0

16384 – 17407

Instances 0 – 1023 in the adapter

Instances 0 – 1023 in the adapter

17408 – 18431

Instances 0 – 1023 in the adapter

Instances 0 – 1023 in Drive 1

18432 – 19455

Instances 0 – 1023 in the slave

Instances 0 – 1023 in Drive 2

19456 – 20479

Not supported

Instances 0 – 1023 in Drive 3

20480 – 21503

Not supported

Instances 0 – 1023 in Drive 4

21504 – 22527

Not supported

Instances 0 – 1023 in the adapter

Attribute
ID

Access
Rule

Name

Data Type

Description

0

Get

Family Code

BYTE

Code identifying the device.

1

Get

Family Text

STRING[16]

Text identifying the device.

2

Set

Language Code

BYTE

0 = English
1 = French
2 = Spanish
3 = Italian
4 = German
5 = Japanese
6 = Portuguese
7 = Mandarin Chinese
8 = Russian
9 = Dutch

3

Get

Product Series

BYTE

1 = A
2 = B …

4

Get

Number of
Components

BYTE

Number of components (e.g., main control
board, I/O boards) in the device.

Advertising