Dlogic command/status words, Appendix, Powerflex 4 and powerflex 40 drives – Rockwell Automation 22-COMM-E EtherNet/IP Adapter User Manual

Page 149

Advertising
background image

Appendix

D

Logic Command/Status Words

Appendix D provides the definitions of the Logic Command/Logic
Status words that are used for some products that can be connected to the
EtherNet/IP adapter. If you do not see the Logic Command/Logic Status
for the product that you are using, refer to your product’s documentation.

Logic Command Word

PowerFlex 4 and PowerFlex 40 Drives

Logic Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command

Description

x Stop

0 = Not Stop
1 = Stop

x

Start

(1)

0 = Not Start
1 = Start

x

Jog

0 = Not Jog
1 = Jog

x

Clear Faults

0 = Not Clear Faults
1 = Clear Faults

x x

Direction

00 = No Command
01 = Forward Command
10 = Reverse Command
11 = No Command

x

Not used

x

Not used

x x

Accel Rate

00 = No Command
01 = Accel Rate 1 Command
10 = Accel Rate 2 Command
11 = Hold Accel Rate

x

x

Decel Rate

00 = No Command
01 = Decel Rate 1 Command
10 = Decel Rate 2 Command
11 = Hold Decel Rate

x

x

x

Reference
Select

000 = No Command
001 = Freq Source = Select
010 = Freq Source = Int. Freq
011 = Freq Source = Comm
100 = Preset Freq 0
101 = Preset Freq 1
110 = Preset Freq 2
111 = Preset Freq 3

x

Not used

(1)

A 0 = Not Stop condition (logic 0) must first be present before a 1 = Start condition will start the drive.

Advertising