Rockwell Automation 22-COMM-E EtherNet/IP Adapter User Manual

Page 20

Advertising
background image

2-2

Installing the Adapter

1. Set the Operating Mode Switch (SW1) for Single or Multi-Drive

operation (see

Figure 2.1

and setting descriptions below). For

complete details on Multi-Drive mode operation, see

Chapter 7

,

Using Multi-Drive Mode

.

Figure 2.1 Setting Single/Multi-Drive Operation and Web Page Enable Switches

2. Set the Web Pages Switch (SW2) to enable or disable the adapter web

pages (see

Figure 2.1

and setting descriptions below). By default, the

adapter web pages are disabled. For complete details on the adapter
web pages, see

Chapter 9

,

Viewing the Adapter’s Web Pages

.

!

ATTENTION: Risk of equipment damage exists. The EtherNet/IP
adapter contains ESD (Electrostatic Discharge) sensitive parts that can
be damaged if you do not follow ESD control procedures. Static control
precautions are required when handling the adapter. If you are
unfamiliar with static control procedures, refer to Guarding Against
Electrostatic Damage
, Publication 8000-4.5.2.

SW1 Setting

Description

Down position
(DN = Closed = 0)

Sets the adapter for Single drive mode (default setting) using a
single drive connection.

Important: In this mode, connections to multiple drives must be
removed since all powered and connected hosts will respond to
any message sent by the adapter.

Up position
(UP = Open = 1)

Sets the adapter for Multi-Drive operation mode using up to 5
different drives. DSI peripherals (22-HIM-*, 22-SCM-*, etc.) do
not operate with the adapter in this mode.

SW2 Setting

Description

Down position
(DN = Closed = 0)

Disables the adapter web pages (default setting).

Up position
(UP = Open = 1)

Enables the adapter web pages.

2

1

OPERATING

MODE SWITCH

Single-Drive

Operation

Position

Multi-Drive

Operation

Position

Disable Web
Position

Enable Web
Position

WEB PAGES
SWITCH