Rockwell Automation 2706-MB1 MESSAGEVIEW 421 SOFTWARE MANUAL User Manual
Page 102
![background image](/manuals/580630/102/background.png)
5–13
Communications Overview
Publication 2706-817
Module groups
The MessageView 421 I/O can occupy
1
/
4
,
1
/
2
,
3
/
4
, or a Full rack.
Each
1
/
4
rack contains two module groups (32 input and 32 output
bits). An entire rack contains 8 module groups that are numbered
from 0 to 7.
Rack #
MessageView I/O
Four 1/4
Rack Sizes
Eight Input/Output
Module Groups
0 1
2 3
4 5
6 7
1
/
4
1
/
4
1
/
4
1
/
4
Input
Output
0 1
2 3
4 5
6 7
Each input or output module group has 16 bits
If a MessageView terminal does not occupy a full rack, another
terminal or device can be configured for the unused modules. For
example:
Parameter
MessageView 421
Other Rack Device
Rack Number
1
1
Starting Module Group
0
6
Rack Size
3
/
4
1
/
4
Last Chassis?
No
Yes
Important: Two I/O systems can not share the same module.
The maximum rack number that can be assigned to the terminal
depends on the type of logic controller.