Rockwell Automation 2706-MB1 MESSAGEVIEW 421 SOFTWARE MANUAL User Manual

Page 56

Advertising
background image

4–8

Planning an Application

Publication 2706-817

MessageView features supported by a logic controller

A MessageView terminal can support the following additional
features when controlled by a PLC or other logic controller:

supporting Handshaking for numeric entry and ACK messages as
well as for latched function keys

supporting bit triggering

supporting Startup and Background messages that contain
embedded display variables

sending Preset or Last values for variables to the controller

ASCII Triggering Device limitations:

If the ASCII network has more than one device, the terminal
operator must not send data (such as Entry variables embedded in
a message) from the MessageView terminal to the ASCII
Triggering device. This could cause data collisions. Consider this
when creating an application for such a network.

Data is sent from a terminal when:

the ACK key is pressed (all terminals)

numeric keys are used (421N and 421F terminals)

an enabled Function key is pressed (421F terminals)

The MessageView terminal supports an output buffer to process
outgoing data responses. The buffer is designed to handle at least
two of the largest responses (such as 20 Ctrl-I responses or 2
messages that contain the maximum of 10 Entry Variables).

If the output buffer becomes full (for instance, if someone
repeatedly presses a Momentary Function Key before the data can
be sent), any new outgoing data is lost until the output buffer is
available again.

ASCII Trigger applications require a value trigger tag name to be
defined. See Page 10–21. Only the tag name is used; the node
address and node name may be left blank. The tag name is used
internally by the MessageView terminal as a reference.

Communication setup

In MessageBuilder software, a logic controller is specified by its
PLC/SLC/Scanner type. An ASCII Triggering device is a single
device that does not require a device type.

Advertising