Safety considerations – Rockwell Automation 2706-MB1 MESSAGEVIEW 421 SOFTWARE MANUAL User Manual

Page 50

Advertising
background image

4–2

Planning an Application

Publication 2706-817

The application designer must make sure that an application cannot
be used in an unsafe manner. Failsafes must be built into each
application.

!

ATTENTION: Do not configure Function Keys as
emergency stops or other controls critical for safe
operation. Use separate hard-wired operator interface
devices.

Refer to “Safety Guidelines for the Application, Installation and
Maintenance of Solid State Controls” (Publication SGI-1.1).

Communications interruptions

The MessageView 421 terminal relies on communications with the
logic controller or ASCII Triggering device.

Communications are interrupted within the terminal when it:

is in the Front Panel Editor mode

is receiving an application download from a personal
computer

has a major fault

loses power

detects that the Remote I/O link has failed.

The logic controller considers the terminal as a faulted I/O rack
when it does not communicate. The controller must be programmed
to cope with this situation. Specifically, it must:

return any machine or process to a safe state

monitor the rack fault bit associated with the MessageView
terminal’s assigned rack.

Refer to the controller’s user manual.

Safety Considerations