Validation Error Messages

D–10

Publication 2706-817

Message

What to do

Meaning

Invalid Tag - Msg #[number] Embedded
Numeric Display Tag [name] Scale value of 0
is not valid.

Scale value of zero is not allowed.

Use the tag editor to change the tag Scale to
be non-zero.

Invalid Tag - Msg #[number] Embedded
Numeric Display Tag [name] must be of type
Output or BTW.

The tag is controlled by the PLC and is read
by the Terminal. The tag must be in the
Output image or be in a BTW (Block Transfer
Write).

Use the tag editor to change the tag address
or the Terminal Setup/Comms. Setup/Block
Transfer dialog to put the tag into a Block
Transfer that has its mode assigned as W.

Invalid Tag - Msg #[number] Embedded
Numeric Display Tag [name] isn’t a valid
address in the terminal’s assigned Discrete
Rack or Block Transfer channels.

The tag address is not in the discrete I/O
image of the rack or in the block transfer(s)
configured for the Terminal.

Use the tag editor to change the tag address
or the Terminal Setup/Comms. Setup/Block
Transfer dialog to put the tag into a Block
Transfer.

Invalid Tag - Msg #[number] Embedded
Numeric Display Tag [name] overlaps
Discrete I/O Rack Control/Status byte.

The tag is assigned the same address as the
Block Transfer Control/Status Byte (the lowest
byte in the discrete I/O rack).

Use the tag editor to enter a different address
for the tag or use the Terminal Setup/Comms.
Setup/Block Transfer dialog to disable block
transfers if they are not being used.

Invalid Tag - Msg #[number] Embedded
Numeric Entry Write Tag [name] Tag minimum
absolute value is too large for Numeric Entry
field width.

The Minimum Data Entry Limit assigned to
the tag will not fit within the Numeric Variable
Entry Field Width.

Use the tag editor to change the Minimum
Data Entry or select the embedded variable in
the message and change the Field Width
using the Format/Edit Variable dialog.

Invalid Tag - Msg #[number] Embedded
Numeric Display Tag [name] Bit address
specified but tag isn’t Bit data type.

The assigned tag is the wrong data type.

Use the tag editor to change the data type of
the tag.

Invalid Tag - Msg #[number] Tag [name]
references device [name] as Node Name.
This is not the Logic Controller selected in
Terminal Setup - Comms. Setup.

The Node Name assigned to this tag used in
this message does not match the assigned
PLC/Scanner Name.

Use the tag editor to change the Node name
for this tag or change the PLC/Scanner Name
in the Terminal Setup/Comms. Setup dialog.

Invalid Tag - Msg #[number] Tag [name]
references no device. Tag Node Name must
match the Logic Controller selected in
Terminal Setup - Comms. Setup.

There is no Node Name assigned to the tag
used in this message.

Use the tag editor to change the Node Name
for this tag.

Invalid Tag - Msg #[number] Undefined
Embedded Numeric Display Tag.

Tag is undefined in the project database.

Use the tag editor to define the tag.

Invalid Tag - Msg #[number] with Embedded
Entry Handshake Tag [name].

Tag is undefined in the project database.

Use the tag editor to change the data type of
the tag, or use the Numeric Entry dialog to
select or add an appropriate tag.

Invalid Tag - Msg #[number] with Embedded
Entry Notify Tag [name].

Tag is undefined in the project database.

Use the tag editor to define the tag.

Invalid Tag - Return Number for Ack Tag
[name] must be of type Unsigned Integer.

The Acknowledge Return Number tag in
Terminal Setup/Control Tags is the wrong
data type.

Use the tag editor to change the data type of
the tag, or use the Terminal Setup Status
Tags dialog to select an appropriate tag.

Invalid Tag - Return Number for FKey Tag
[name] must be of type Unsigned Integer.

The Function Key Return Number tag in
Terminal Setup/Control Tags is the wrong
data type.

Use the tag editor to change the data type of
the tag, or use the Terminal Setup Status
Tags dialog to select an appropriate tag.

Invalid Tag - Second Read Tag [name] must
be of type Unsigned Integer.

The assigned tag is the wrong data type.

Use the tag editor to change the data type of
the tag, or use the Application/Special
Messages/Read Tags dialog to select an
appropriate tag.

Invalid Tag - Second Write Tag [name] must
be of type Unsigned Integer.

The assigned tag is the wrong data type.

Use the tag editor to change the data type of
the tag, or use the Application/Special
Messages/Write Tags dialog to select an
appropriate tag.

Invalid Tag - Tag [name] Bit address specified
but tag isn’t Bit data type.

The assigned tag is the wrong data type.

Use the tag editor to change the data type of
the tag.