Validation Error Messages

D–5

Publication 2706-817

Message

What to do

Meaning

Invalid Tag - Acknowledge-Handshake Tag
[name] isn’t a valid address in the terminal’s
assigned Discrete Rack or Block Transfer
channels.

The Acknowledge-Handshake Tag in Terminal
Setup/Control Tags address is not in the
discrete I/O image of the rack or in the block
transfer(s) configured for the Terminal.

Use the tag editor to change the tag address
or the Terminal Setup/Comms. Setup/Block
Transfer dialog to put the tag into a Block
Transfer.

Invalid Tag - Acknowledge-Handshake Tag
[name] must be of type Output or BTW.

The tag is controlled by the PLC and is read
by the Terminal. The tag must be in the
Output image or be in a BTW (Block Transfer
Write).

Use the tag editor to change the tag address
or the Terminal Setup/Comms. Setup/Block
Transfer dialog to put the tag into a Block
Transfer that has its mode assigned as W.

Invalid Tag - Acknowledge-Handshake Tag
[name] overlaps Discrete I/O Rack
Control/Status byte.

The Acknowledge-Handshake Tag in Terminal
Setup/Control Tags is assigned the same
address as the Block Transfer Control/Status
Byte (the lowest byte in the discrete I/O rack).

Use the tag editor to change the tag address
or the Terminal Setup/Comms. Setup/Block
Transfer dialog to disable block transfers if
they are not being used.

Invalid Tag - Acknowledge-Handshake Tag
[name].

Tag is undefined in the project database.

Use the tag editor to define the tag.

Invalid Tag - Bit Trigger Tag [name].

Tag is undefined in the project database.

Use the tag editor to define the tag.

Invalid Tag - Bit Trigger Tag [name] isn’t a
valid address in the terminal’s assigned
Discrete Rack or Block Transfer channels.

The tag address is not in the discrete I/O
image of the rack or in the block transfer(s)
configured for the Terminal.

Use the tag editor to change the tag address
or the Terminal Setup/Comms. Setup/Block
Transfer dialog to put the tag into a Block
Transfer.

Invalid Tag - Bit Trigger Tag [name] must be of
type Output or BTW.

The tag is controlled by the PLC and is read
by the Terminal. The tag must be in the
Output image or be in a BTW (Block Transfer
Write).

Use the tag editor to change the tag address
or the Terminal Setup/Comms. Setup/Block
Transfer dialog to put the tag into a Block
Transfer that has its mode assigned as W.

Invalid Tag - Bit Trigger Tag [name] must be of
type Unsigned Integer.

The assigned tag is the wrong data type.

Use the tag editor to change the data type of
the tag.

Invalid Tag - Bit Trigger Tag [name] overlaps
Discrete I/O Rack Control/Status byte.

The tag is assigned the same address as the
Block Transfer Control/Status Byte (the lowest
byte in the discrete I/O rack).

Use the tag editor to change the tag address
or the Terminal Setup/Comms. Setup/Block
Transfer dialog to disable block transfers if
they are not being used.

Invalid Tag - Bit Trigger Tag [name] will not fit
in the Block Transfer Table (Max Bit Trigger =
[number]) or tag is not defined in the Table.

The tag will not fit within the valid range in the
discrete I/O image of the rack or in the block
transfer(s) configured for the Terminal.

Redefine the block transfer address or reduce
the total number of bit triggered messages.

Invalid Tag - Block [number] for Tag [name].

Address defined in the block transfer is
incorrect.

Use the Communication Setup Block Transfer
dialog to define the proper address.

Invalid Tag - Brightness Level Tag [name]
must be of type Output or BTW.

The tag is controlled by the PLC and is read
by the Terminal. The tag must be in the
Output image or be in a BTW (Block Transfer
Write).

Use the tag editor to change the tag address
or the Block Transfer dialog to put the tag into
a BTW.

Invalid Tag - Brightness Level Tag [name]
must be of type Unsigned Integer.

The assigned tag is the wrong data type.

Use the tag editor to change the data type of
the tag.

Invalid Tag - Brightness Level Tag [name] isn’t
a valid address in the terminal’s assigned
Discrete Rack or Block Transfer channels.

The tag address is not in the discrete I/O
image of the rack or in the block transfer(s)
configured for the Terminal.

Use the tag editor to change the tag address
or the Communication Setup Block Transfer
dialog to put the tag into a Block Transfer.

Invalid Tag - Brightness Level Tag [name]
overlaps Discrete I/O Rack Control/Status
byte.

The tag is assigned the same address as the
Block Transfer Control/Status Byte (the lowest
byte in the discrete I/O rack).

Use the tag editor to change the tag address
or the Terminal Setup/Comms. Setup/Block
Transfer dialog to disable block transfers if
they are not being used.

Invalid Tag - Day Read Tag [name] must be of
type Unsigned Integer.

The assigned tag is the wrong data type.

Use the tag editor to change the data type of
the tag, or use the Application/Special
Messages/Read Tags dialog to select an
appropriate tag.