Planning an Application

Publication 2706-817

Scaled Data Display Variables take raw numeric values and
mathematically manipulate them so the values can be shown in
standard units such as:

gallons

feet per second

pounds per square inch.

Values from the logic controller address are scaled using the formula:

y = mx + b

y = scaled (displayed) value

m = scale (multiplier)

x = value stored in controller address

b = offset.

The scale and offset values are entered in the Tag Editor.

Example: Scaling a Display Variable

Flow Rate
Transducer
Value

510

Valve #1

Flow Rate
Transducer

510

Controller

13
Scaling
(x 0.0059 + 10)

Note: Messages sent to slave devices may contain scaled variables.
The variable tag contains the scaling information.

Scaling Data Display
Variables