10–28
Terminal and Communication Setup
Publication 2706-817
4. Set the parameter values as needed.
Parameters
Default
Options
Baud Rate
9600
300, 600, 1200, 2400, 9600, 19,200,
38,400 bps
Data Bits
8
7, 8
Parity
None
None, Odd, Even
Stop Bits
1
1, 2
H/W Handshake
Disabled
Enabled, Disabled
Inter-Packet Delay
200 ms
50, 100, 150, 200, 250, 300, 350,
400, 450, 500 ms
For information on the Hardware Handshake parameter, see Page
4–29.
Note: The Inter-Packet Delay parameter is intended to allow a
Dataliner DL10, DL20 or DL50 time to process each message
packet before the next packet is sent from the master. The worst
case for the Dataliner family is 300 ms.
If the port is configured for an ASCII Input device, this option
does not apply.
5. Select OK to save the RS-232 settings and return to the Terminal
Setup dialog.