Validation Error Messages

D–9

Publication 2706-817

Message

What to do

Meaning

Invalid Tag – Msg #[number] Embedded Entry
Write Tag [name] Min Data Entry Limit is
smaller than the allowed value for this tag
type.

The assigned tag minimum Data Entry Limit is
invalid.

Use the tag editor to change the Minimum
entry value.

Invalid Tag – Msg #[number] Embedded Entry
Write Tag [name] Minimum Data Entry
exceeds data limits (-2147483647 to
+2147483647).

The assigned tag minimum entry is less than
the minimum value allowed.

Use the tag editor to change the Minimum
Data Entry value.

Invalid Tag - Msg #[number] Embedded Entry
Write Tag [name] Scale value of 0 or not in
range (

".0001 to "9999.0).

The tag scaling factors are outside the valid
range.

Use the tag editor to change the tag scale.

Invalid Tag - Msg #[number] Embedded Entry
Write Tag [name].

Tag is undefined in the project database.

Use the tag editor to define the tag.

Invalid Tag - Msg #[number] Embedded Entry
Write Tag [name] used but not defined.

Tag is undefined in the project database.

Use the tag editor to define the tag.

Invalid Tag - Msg #[number] Embedded Entry
Write Tag [name] has wrong type.

The assigned tag is the wrong data type.

Use the tag editor to change the data type of
the tag.

Invalid Tag - Msg #[number] Embedded Entry
Write Tag [name] initial value must be an
integer.

The assigned tag is the wrong data type.

Use the tag editor to change the data type of
the tag.

Invalid Tag - Msg #[number] Embedded Entry
Write Tag [name] isn’t a valid address in the
terminal’s assigned Discrete Rack or Block
Transfer channels.

The tag address is not in the discrete I/O
image of the rack or in the block transfer(s)
configured for the Terminal.

Use the tag editor to change the tag address
or the Communication Setup Block Transfer
dialog to put the tag into a Block Transfer.

Invalid Tag - Msg #[number] Embedded Entry
Write Tag [name] Max value not valid or not in
range.

The assigned tag maximum value is invalid.

Use the tag editor to change the Maximum
entry value.

Invalid Tag - Msg #[number] Embedded Entry
Write Tag [name] Min value not valid or not in
range.

The assigned tag minimum value is invalid.

Use the tag editor to change the Minimum
entry value.

Invalid Tag - Msg #[number] Embedded Entry
Write Tag [name] must be of type Input or
BTR.

The tag is controlled by the Terminal and is
read by the PLC. The tag must be in the Input
image or be in a BTR (Block Transfer Read).

Use the tag editor to change the tag address
or the Terminal Setup/Comms. Setup/Block
Transfer dialog to put the tag into a Block
Transfer that has its mode assigned as R.

Invalid Tag - Msg #[number] Embedded Entry
Write Tag [name] offset not in range.

The tag offset value is outside the range of
–32768 and +32767.

Use the tag editor to change the tag offset.

Invalid Tag - Msg #[number] Embedded Entry
Write Tag [name] overlaps Discrete I/O Rack
Control/Status byte.

The tag is assigned the same address as the
Block Transfer Control/Status Byte (the lowest
byte in the discrete I/O rack).

Use the tag editor to enter a different address
for the tag or use the Terminal Setup/Comms.
Setup/Block Transfer dialog to disable block
transfers if they are not being used.

Invalid Tag - Msg #[number] Embedded
Numeric Display Tag [name].

Tag is undefined in the project database.

Use the tag editor to define the tag.

Invalid Tag - Msg #[number] Embedded
Numeric Display Tag [name] has wrong type.

The Embedded Numeric Display Tag must be
a signed integer, unsigned integer, or bit data
type.

Use the tag editor to change the data type of
the tag, or select the embedded variable in
the message and select the appropriate tag
using the Format/Edit Variable dialog.

Invalid Tag - Msg #[number] Embedded
Numeric Display Tag [name] isn’t a valid
address in the terminal’s assigned Discrete
Rack or Block Transfer channels.

The tag address is not in the discrete I/O
image of the rack or in the block transfer(s)
configured for the Terminal.

Use the tag editor to change the tag address
or the Terminal Setup/Comms. Setup/Block
Transfer dialog to put the tag into a Block
Transfer.