Rockwell Automation 2706-MB1 MESSAGEVIEW 421 SOFTWARE MANUAL User Manual

Page 110

Advertising
background image

5–21

Communications Overview

Publication 2706-817

Example: Block Transfer Write

In this example, the MessageView 421 terminal is assigned to rack
#3 and its starting module group is 0. A Numeric Variable Display
variable has the address N7:0, and its value is written by the logic
controller to a portion of the data block being transferred.

BTW

(EN)

BLOCK TRANSFER WRITE
Rack 03
Group 0
Module 0
Control Block N16:1
Data File N7:0
Length 10
Continuous N

The PLC receives and stores data from
an input device, in this example a flow
sensor.

The PLC ladder logic program initiates a
block transfer of a data block (10 words)
containing the display data.

Display variable with
Tag Name “Flow_Rate” from
Address N7:5

The MessageView terminal receives the data and
determines the starting address where the data is
written by matching the block size with the address
entered in the Communication Setup utility.

The MessageView updates the Numeric Variable
Display using the data from the controller.

Flow Rate
Transducer

Data From
PLC

N7:5

10 WORDS

N7:0
N7:1
N7:2
N7:3
N7:4
N7:5
N7:6
N7:7
N7:8
N7:9

Flow Rate Data

The MessageView now carries a copy of that
segment of the logic controllers data table.

Tag Name = Flow_Rate

Advertising