Validation Error Messages

D–8

Publication 2706-817

Message

What to do

Meaning

Invalid Tag - Msg #[number] Embedded Entry
Handshake Tag [name] Bit address specified
but tag isn’t Bit data type.

The assigned tag is the wrong data type.

Use the tag editor to change the data type of
the tag, or use the Numeric Entry dialog to
select or add an appropriate tag.

Invalid Tag - Msg #[number] Embedded Entry
Handshake Tag [name] must be of type Bit.

The assigned tag is the wrong data type.

Use the tag editor to change the data type of
the tag.

Invalid Tag - Msg #[number] Embedded Entry
Handshake Tag defined without Embedded
Entry Notification Tag.

Tag is undefined in the project database.

Use the tag editor to change the data type of
the tag, or use the Numeric Entry dialog to
select or add an appropriate tag.

Invalid Tag - Msg #[number] Embedded Entry
Handshake Tag [name] must be of type
Output or BTW.

The tag is controlled by the PLC and is read
by the Terminal. The tag must be in the
Output image or be in a BTW (Block Transfer
Write).

Use the tag editor to change the tag address
or the Terminal Setup/Comms. Setup/Block
Transfer dialog to put the tag into a Block
Transfer that has its mode assigned as W.

Invalid Tag - Msg #[number] Embedded Entry
Handshake Tag [name] isn’t a valid address in
the terminal’s assigned Discrete Rack or
Block Transfer channels.

The tag address is not in the discrete I/O
image of the rack or in the block transfer(s)
configured for the Terminal.

Use the tag editor to change the tag address
or the Communication Setup Block Transfer
dialog to put the tag into a Block Transfer.

Invalid Tag - Msg #[number] Embedded Entry
Handshake Tag [name] overlaps Discrete I/O
Rack Control/Status byte.

The tag is assigned the same address as the
Block Transfer Control/Status Byte (the lowest
byte in the discrete I/O rack).

Use the tag editor to enter a different address
for the tag or use the Terminal Setup/Comms.
Setup/Block Transfer dialog to disable block
transfers if they are not being used.

Invalid Tag - Msg #[number] Embedded Entry
Notification Tag defined without Embedded
Entry Handshake Tag.

The tag is undefined in the project database.

Use the tag editor to define the tag.

Invalid Tag - Msg #[number] Embedded Entry
Notify Tag [name] isn’t a valid address in the
terminal’s assigned Discrete Rack or Block
Transfer channels.

The tag address is not in the discrete I/O
image of the rack or in the block transfer(s)
configured for the Terminal.

Use the tag editor to change the tag address
or the Terminal Setup/Comms. Setup/Block
Transfer dialog to put the tag into a Block
Transfer.

Invalid Tag - Msg #[number] Embedded Entry
Notify Tag [name] must be of type Bit.

The assigned tag is the wrong data type.

Use the tag editor to change the data type of
the tag, or use the Terminal Setup Status
Tags dialog to select an appropriate tag.

Invalid Tag - Msg #[number] Embedded Entry
Notify Tag [name] overlaps Discrete I/O Rack
Control/Status byte.

The tag is assigned the same address as the
Block Transfer Control/Status Byte (the lowest
byte in the discrete I/O rack).

Use the tag editor to enter a different address
for the tag or use the Terminal Setup/Comms.
Setup/Block Transfer dialog to disable block
transfers if they are not being used.

Invalid Tag - Msg #[number] Embedded Entry
Write Tag [name] Bit address specified but tag
isn’t Bit data type.

The assigned tag is the wrong data type.

Use the tag editor to change the data type of
the tag.

Invalid Tag – Msg #[number] Embedded Entry
Write Tag [name] Initial Value exceeds the
allowed value for this tag type.

The assigned tag initial value is outside of the
valid range.

Use the tag editor to change the tag initial
value.

Invalid Tag – Msg #[number] Embedded Entry
Write Tag [name] Max Data Entry Limit
exceeds the allowed value for this tag type.

The assigned tag maximum Data Entry Limit
is invalid.

Use the tag editor to change the Maximum
entry value.

Invalid Tag – Msg #[number] Embedded Entry
Write Tag [name] Max Entry value must be
greater than Min Entry value.

The assigned tag minimum Data Entry Limit is
greater than the maximum Data Entry Limit.

Use the tag editor to change the Maximum or
Minimum entry values.

Invalid Tag – Msg #[number] Embedded Entry
Write Tag [name] Maximum Data Entry
exceeds data limits (-2147483647 to
+2147483647).

The assigned tag maximum entry is greater
than the maximum value allowed.

Use the tag editor to change the Maximum
Data Entry value.