Installing MessageBuilder Software

Publication 2706-817

3. Select the Add Device button to add and open the configuration

dialog for the selected driver.

For example, if you select DF1 on COM Port this dialog opens:

Unique number assigned to

INTERCHANGE driver

(This is not the computer’s COM port.)

Default Driver Name
(can be edited)

Disables driver configuration
without removing it from
Configured Drivers list.

COM Port = 1 and Interrupt = 4, or
COM Port = 2 and Interrupt = 3

DF1 parameters must be set to:

Baud:

Parity:

Error Detect:

19200

None

CRC

Typical:

Note: Consult your personal computer’s user manual for COM
Port Interrupt settings.

4. Edit parameters and select OK when done.

The parameters are specific to the communications card installed
in your computer, or to the type of connection you will be using
to transfer files.

The configured driver appears under the Configured Devices: list
in the Driver Configuration dialog.

Important: Do not configure more than one driver for the same

communication port.

5. Reboot your computer to load the driver and its configuration.

Important: You must reboot your computer any time you add or

remove a driver or change configuration parameters of a
driver.

Exiting Windows and re-entering will not load the
driver.