Validation Error Messages

D–2

Publication 2706-817

Message

What to do

Meaning

Embedded ASCII Character 13 is not allowed.

The embedded ASCII Character of value 13
is not allowed for slaving messages.

Remove or change the value of the
embedded ASCII character 13 by selecting
the embedded ASCII character in the
message and pressing the Delete key, or
selecting the Format/Edit Variable Dialog.

Embedded ASCII Entry Tag array size must
be greater than ASCII Entry variable field
width.

The assigned tag array size is smaller than
the display field width. Operator input cannot
be completed without a large character array
defined.

Use the tag editor to change the tag array
size.

Embedded Carriage-Return not allowed with
“Full” size text.

The message with “Full” attribute can not
contain embedded Carriage-Return.

Use the Message Editor Table view to change
the text size or remove the embedded
Carriage-Return from the message.

Embedded Display Variables are not allowed
in Chained message [number], chained from
message [number].

Applications can not support embedded
displayable variables in a chained-to
message.

Resolve the conflict by chaining to a different
message or removing the embedded display
variables in the chained-”To” message.

Embedded Display Variables are not allowed
in the Background message.

The Background Message assigned that has
embedded display variables is not allowed.

Change or disable the Background Message
in the Terminal Setup/Advanced dialog or
remove the embedded display variables from
the message.

Embedded Display Variables are not allowed
in the Startup message.

The Startup Message assigned that has
embedded display variables is not allowed.

Change or disable the Startup Message in the
Terminal Setup/Advanced dialog or remove
the embedded display variables from the
message.

Embedded Entry Write Tag used but not
defined.

The tag is undefined in the project database.

Use the tag editor to define the tag.

Embedded Graphic 13 is not allowed in slave
messages.

The embedded Graphic symbol number 13 is
not allowed for slaving messages.

Remove or change the value of the
embedded Graphic number 13 by selecting
the embedded Graphic in the message and
pressing the Delete key or selecting the
Format/Edit Variable Dialog.

Embedded-Carriage-Return not allowed
without All attribute set.

Embedded Carriage-Return requires “All”
attribute enabled.

Use the Message Editor Table view to change
the Line attribute to “ALL” or remove the
embedded Carriage-Return from the
message.

ББББББББББББ

Б

ББББББББББ

Б

Б

ББББББББББ

Б

ББББББББББББ

Error: Msg [number] Numeric Variable Entry is
not supported by terminal type.

БББББББББББ

Б

БББББББББ

Б

Б

БББББББББ

Б

БББББББББББ

The terminal is a 421D type.

ББББББББББББ

Б

ББББББББББ

Б

Б

ББББББББББ

Б

ББББББББББББ

Remove Numeric Entry variables from the
messages listed. Or if practical change the
application to a different terminal type.

Error: “Return Message Number to PLC”
checked in the Advanced dialog requires Msg
Tags Return Number, Ack Tags Return
Number or FKey Tag Return Number be
defined.

An appropriate return message number tag
must be defined if Return Message Number
to PLC option is selected.

Remove the Return Message Number to PLC
option in the Terminal Setup/Advanced dialog
or define a return message number tag in the
Terminal Setup/Control Tags dialog.

Field width of Entry is larger than the width of
the display.

An entry is not allowed to be wider than the
displayable area.

Reduce the embedded Variable Entry Field
width or increase the display width by making
the message Text Size Half or Quarter.

ББББББББББББ

Б

ББББББББББ

Б

ББББББББББББ

Function Key Write Tag missing or tag not
assigned.

БББББББББББ

Б

БББББББББ

Б

БББББББББББ

The Function Key Write Tag is undefined for
one or more Function Keys that are enabled
in the Application.

ББББББББББББ

Б

ББББББББББ

Б

ББББББББББББ

Use the Function Key dialog to define a Write
Tag for each Function Key that is enabled in
the Application.

Graphic does not display properly on the end
of the line.

The defined message cannot be displayed
properly.

Reformat the message by deleting
characters, or enable the scrolling attribute.