Setting advanced terminal options – Rockwell Automation 2706-MB1 MESSAGEVIEW 421 SOFTWARE MANUAL User Manual

Page 220

Advertising
background image

10–12

Terminal and Communication Setup

Publication 2706-817

The Advanced tab in the Terminal Setup dialog allows the
application designer to define a variety of global configuration
parameters for the MessageView terminal.

To set or modify advanced terminal options:

1. Select the Advanced tab from the Terminal Setup dialog.

2. Modify the settings as needed.

3. Select the OK button to save all the settings from the Terminal

Setup dialog and return to the main Message Editor Table View.

Or select another tab and continue setting up the terminal for the
application.

Or select the Cancel button to return to the Message Editor Table
View without saving any Terminal Setup settings.

Return Message Number to PLC

If this option is enabled, the message number of the displayed
message is sent to the controller, provided its global Return Message
Number tag is defined. The controller may be a logic controller or an
ASCII Triggering device.

The three classes of messages may have Return Number tags:

messages with the Ack attribute enabled

messages with Function Keys enabled

messages of all other kinds.

Note: If the Return Message Number to PLC attribute is enabled,
then one or more of the three Return Number tags in the Control
Tags tab must be defined. See Page 10–21.

If the controller is an ASCII Triggering device, the Return Message
Number is sent back as part of the Ctrl-N message. See Page 5–12.