Chapter 1 Prepare the Kinetix 350 Drive Hardware

Wire the Back-up Power Connector

You need a user-supplied, external 24V DC power supply to provide back-up power to the drive.
Complete these steps to wire the BP connector.

1.

Verify the user-supplied, external power supply is not powered.

2.

Remove the BP connector from
the drive.

3.

Remove approximately 6 mm (0.25
in.) insulation from two 1.5 mm

2

(16 AWG) copper wires.

4.

Connect a wire from a +24V DC
terminal on the external power
supply to the +24V DC terminal
on the BP connector.

5.

Connect a wire from a -24C DC terminal on the external power supply to the -24V DC
terminal on the BP connector.

6.

Insert the connector plug into the drive in the location shown above.

IMPORTANT

Do not connect power to the external power supply.

+

24

-

+24V DC

-24V DC