Chapter 1 Prepare the Kinetix 350 Drive Hardware

Complete these steps to assign an IP address to your 2097-V31PR2-LM drive.

1.

Apply power to the drive via the 120V AC power source described in

Wire the Input Power

Connector on page 23

.

Do not apply power to the BP connector yet.

2.

Press .

3.

Use

to access parameter DHCP.

The display indicates each parameter as you use the up/down arrows to scroll all options.

4.

Check this parameter is set to a value of 0.

5.

If the DHCP parameter is set to 1, then use

and

to set to 0.

6.

Cycle power to the drive.

The change takes effect. Unless DHCP mode is enabled in the future, each time power is cycled
to the drive, it uses the IP address that was manually assigned.

Your 2097-V31PR2-LM drive ships from the factory with its IP address set at 192.168.124.200.
To complete the tasks described in this quick start, you must change the IP address to
192.168.1.5

.