Add a Kinetix 350 Drive to an RSLogix 5000 Project Chapter 2

Apply Power to the Kinetix 350 Drive System

Before beginning this section, verify that you have wired and configured your Kinetix 350 drive
and your controller’s EtherNet/IP network port correctly.

Complete these steps to apply power to the Kinetix 350 drive system.

1.

Disconnect the load to the MPL-A310P-MJ72AA motor.

2.

Apply 120V AC main input power to the 2097-V31PR2-LM drive’s IPD connector.

3.

Verify the four-character status indicator is initially 00 and then transitions to scrolling the
drive’s IP address.

If so, proceed to the next step.

If the status indicator is blank,
return to

step 2

.

4.

Apply 24V DC power to the
2097-V31PR2-LM drive’s BP
connector.

SHOCK HAZARD: To avoid hazard of electrical shock, perform all mounting and wiring of the
Bulletin 2097 drive prior to applying power.

Once power is applied, connector terminals may have voltage present even when not in use.

ATTENTION: To avoid personal injury or damage to equipment, disconnect the load to the
motor. Make sure each motor is free of all linkages when initially applying power to the system.

Four-character
Status Indicators

Data Entry Status
Indicator