Rockwell Automation Publication IASIMP-QS032A-EN-P - March 2012

25

Prepare the Kinetix 350 Drive Hardware Chapter 1

Apply the Motor Cable Shield Clamp

Complete these steps to apply the motor cable shield clamp.

1.

Locate a position for installing the cable shield clamp within 50…75 mm (2…3 in.) of
the drive.

2.

Lay out and drill holes for the cable clamp.

3.

Locate the position on the motor power cable that comes under the clamp and remove
about an inch of the cable jacket to expose the shield braid.

4.

Position the exposed portion of the cable braid directly in line with the clamp.

5.

Clamp the exposed shield to the panel by using the clamp and two #6-32 x 1 screws
provided with your drive.

ATTENTION: Plan the installation of your system so that you can perform all cutting, drilling,
tapping, and welding with the system removed from the enclosure. Because the system is of
the open type construction, be careful to keep any metal debris from falling into it. Metal debris
or other foreign matter can become lodged in the circuitry, which can result in damage to
components.

25 mm

(1.0) in.

If panel is painted, remove paint to
provide metal-to-metal contact.

34 mm

(1.34) in.

Motor Power Ground Shield Clamp

12.7 mm
(0.50) in.

50…75 mm
(2…3 in.)

50…75 mm
(2…3 in.)

Advertising