Flux braking, Clearing the fault queue, Fault configuration – Rockwell Automation 20B PowerFlex 70, PowerFlex 700 Reference Manual User Manual

Page 103: Power up marker

Advertising
background image

Flux Braking

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

103

Resetting faults will clear the faulted status indication. If any fault condition still
exists, the fault will relatch and another entry made in the fault queue.

Clearing the Fault Queue

Performing a fault reset does not clear the fault queue. Clearing the fault queue is
a separate action.

Fault Configuration

The drive can be configured such that some fault conditions do not trip the drive.
Configurable faults include those that are user inputs.

[Fault Config 1] is a bit-mapped 16 bit word enabling or disabling certain fault
conditions (see below). Disabling a fault removes the effect of the fault condition
and makes the event unknown to the user. If the bit is on, the fault is enabled. If
the bit is off, the fault is not enabled.

Power Up Marker

Copy of factory “drive under power” timer at the last power-up of the drive. Used
to provide relevance of Fault 'n' Time values with respect to the last power-up of
the drive.

This value will rollover to 0 after the drive has been powered on for more than
the hours shown in the Range field (approximately 47.667 years).

Flux Braking

You can use flux braking to stop the drive or to shorten the

deceleration time to a lower speed. Other methods of deceleration or stopping
may perform better depending on the motor and the load.

To enable flux braking:

1.

[Bus Reg Mode A, B] must be set to “1” Adjust Freq to enable the bus
regulator.

2.

[Flux Braking] must be set to 1 “Enabled”.

When enabled, flux braking automatically increases the motor flux resulting in an
increase of motor losses. The flux current is only increased when the bus voltage
regulator is active. When the bus voltage regulator is not active, the flux current is
returned to normal. The maximum flux current is equal to rated motor current
but may be further reduced depending on the load level, IT protection, or current

1

x

1

0

0

0

1

0

0

0

x

0

0

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1

=Enabled

0

=Disabled

x =Reserved

Bit #

Factory Default Bit Values

Po

wer Loss

UnderV

olta

ge

Motor OverLd

Shear Pin

A

utRst T

ries

Decel Inhibt

Motor Therm

*

In PhaseLoss *

Load Loss *

ShearPNo Acc *

Out PhaseLoss *

* Vector firmware 3.001 & later

Vector