After a drive has been configured for a given application the user can store a copy
of all of the parameter settings in a specific EEPROM area known as a “User Set.”
Up to 3 User Sets can be stored in the drives memory to be used for backup, batch
“switching” or other needs. All parameter information is stored. The user can
then recall this data to the active drive operating memory as needed. Each User
Set can also be identified with a programmable name, selected by the user for
clarity.
Two operations are available to manage User Sets, “Save To User Set” and
“Restore From User Set.” The user selects 1, 2, or 3 as the area in which to store
data. After data is successfully transferred, “Save User Set” returns to a value of 0.
To copy a given area back into the active EEprom memory, the user selects Set 1,
2, or 3 for “Restore User Set.” After data is successfully transferred, “Restore User
Set” returns to a value of 0. When shipped from the factory all user sets have the
same factory default values. Reset Defaults does not effect the contents of User
Sets.
Important:
User Sets can only be transferred via the HIM. No provisions exist
for control via digital I/O or communications module.
Figure 61 User Sets
Drive Rating & Motor
Parameters
1
2
3
Non Drive Rating & Motor
Parameters
1
2
3
User Set 1
User Set 3
User Set 2
Flash Memory
Flash Memory
Active EE
Reset Defaults
Reset
Active EE
Load
Application
Set
Application Set
RestoreUserSet
SaveUserSet
Save
User set
Restore
User set
400V
Default Data
Factory
Default Data
480V
Default Data
PowerBoard