Start-Up

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

183

Figure 45 PowerFlex 70 & 700 Standard Control Option Startup (5)

StartUp
5. Speed Control

Enter value for

Speed Ref A Hi

60.0 Hz
xxx.x < yyy.y

StartUp
5. Speed Control

Enter value for

Speed Ref A Lo

0.0 Hz
xxx.x < yyy.y

StartUp
5. Speed Control

Enter choice for
Speed Control

<Analog Input>
Comm Adapter
Local HIM-Port 1
Remote HIM
Preset Speeds
MOP

Basic Start Up (Speed Control)

StartUp
5. Speed Control

This section
defines a source
from which to control
speed.

5-0

5-1

5-21

5-24

StartUp
5. Speed Control

Enter choice for
Signal Type

Voltage
Current

Enter

StartUp
5. Speed Control

Enter value for

Analog In 1 Hi

10.0 V
xxx.x < yyy.y

StartUp
5. Speed Control

Enter value for

Analog In 1 Lo

0.0 V
xxx.x < yyy.y

5-18

5-20

5-23

Go to 0-1 (6)

StartUp
5. Speed Control

Save MOP speed
at power down ?

<Yes>
No

PF70 StartUp
5. Speed Control

Enter value for

MOP Rate

5.0 Hz
xx.x < yy.y

Enter

5-15

5-17

Analog
Input 1

StartUp
5. Speed Control

Enter choice for
Input Signal

Analog Input 1
Analog Input 2

5-13

Analog Input

Enter

StartUp
5. Speed Control

Enter value for

Speed Ref A Hi

60.0 Hz
xxx.x < yyy.y

StartUp
5. Speed Control

Enter value for

Speed Ref A Lo

0.0 Hz
xxx.x < yyy.y

5-28

5-31

StartUp
5. Speed Control

Enter choice for
Signal Type

Voltage
Current

Enter

StartUp
5. Speed Control

Enter value for

Analog In 2 Hi

10.0 V
xxx.x < yyy.y

StartUp
5. Speed Control

Enter value for

Analog In 2 Lo

0.0 V
xxx.x < yyy.y

5-24

5-27

5-30

Enter

Analog
Input 2

StartUp
5. Speed Control

Enter choice for
Comm Adapter

Port 5-internal
Port 2-external
Port 3-external

5-2

StartUp
5. Speed Control

Enter choice for
Remote HIM

Port 2 (common)
Port 3

5-3

StartUp
5. Speed Control

Make a selection

.

<Preset Speed 1>
Preset Speed 2
Preset Speed 3
Preset Speed 4
Preset Speed 5
Preset Speed 6
Preset Speed 7
Done

StartUp
5. Speed Control

Enter value for

Preset Speed 1

5.0 Hz
xxx.x < yyy.y

5-12

5-4

StartUp
5. Speed Control

Enter value for

Preset Speed 2

10.0 Hz
xxx.x < yyy.y

5-5

StartUp
5. Speed Control

Enter value for

Preset Speed 3

15.0 Hz
xxx.x < yyy.y

5-6

StartUp
5. Speed Control

Enter value for

Preset Speed 4

20.0 Hz
xxx.x < yyy.y

5-7

StartUp
5. Speed Control

Enter value for

Preset Speed 5

25.0 Hz
xxx.x < yyy.y

5-8

StartUp
5. Speed Control

Enter value for

Preset Speed 6

30.0 Hz
xxx.x < yyy.y

5-9

StartUp
5. Speed Control

Enter value for

Preset Speed 7

35.0 Hz
xxx.x < yyy.y

5-10

Remote

HIM

Preset

Speeds

Go to 0-1 (6)

StartUp
5. Speed Control

Digital Inputs
5 & 6 will be
set to MOP Inc &
MOP Dec.

5-14

StartUp
5. Speed Control

Save MOP speed
at stop ?

<Yes>
No

5-16

Enter

Enter

Enter

Done

Enter

Enter

Preset

Speed 1

Preset

Speed 2

Preset

Speed 3

Preset

Speed 4

Preset

Speed 5

Preset

Speed 6

Preset

Speed 7

Enter

Enter

Enter

Enter

Go to 0-1 (6)

Local HIM-

Port 1

MOP

Enter/

Backup

StartUp
5. Speed Control

The next two
parameters link
a low speed
with a low
analog value.

5-22

StartUp
5. Speed Control

The next two
parameters link
a low speed
with a low
analog value.

5-29

Enter

Enter

StartUp
5. Speed Control

The next two
parameters link
a high speed
with a high
analog value.

5-19

StartUp
5. Speed Control

The next two
parameters link
a high speed
with a high
analog value.

5-26

Enter

Enter

Enter

StartUp
5. Speed Control

Note: Factory default
settings
provide preset
speed operation
from the digital
inputs, unless
you change
their function.

Enter

Enter

Adapter

5-11

5-25

Advertising
This manual is related to the following products: