Cable, control, Cable, motor lengths, Cable, power – Rockwell Automation 20B PowerFlex 70, PowerFlex 700 Reference Manual User Manual

Page 61: Cable trays and conduit, Table 4

Advertising
background image

Cable, Control

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

61

If [Bus Reg Mode A], parameter 161 is set to “Both-DB 1st”

Both regulators are enabled, and the operating point of the Dynamic Brake
Regulator is lower than that of the Bus Voltage Regulator. The Bus Voltage
Regulator setpoint follows the “DB Turn On” curve (

Table 3

). The Dynamic

Brake Regulator follows the “DB Turn On” and turn off curves (

Table 3

). For

example, with a DC Bus Memory at 684V DC, the Bus Voltage Regulator
setpoint is 750V DC and the Dynamic Brake Regulator will turn on at 750V DC
and back off at 742V DC.

Table 4

Cable, Control

Refer to “

Wiring and Grounding Guidelines for Pulse Width Modulated (PWM)

AC Drives,” publication DRIVES-IN001 for detailed information on Cable,
Control.

Cable, Motor Lengths

Refer to “

Wiring and Grounding Guidelines for Pulse Width Modulated (PWM)

AC Drives,” publication DRIVES-IN001 for detailed information on Cable,
Motor Lengths.

Cable, Power

Refer to “

Wiring and Grounding Guidelines for Pulse Width Modulated (PWM)

AC Drives,” publication DRIVES-IN001 for detailed information on Cable,
Power.

Cable Trays and Conduit

Refer to “

Wiring and Grounding Guidelines for Pulse Width Modulated (PWM)

AC Drives,” publication DRIVES-IN001 for detailed information on Cable
Trays and Conduit.

Voltage Class

DC Bus Memory

Bus Reg Curve #1

Bus Reg Curve #2

240

< 325V DC

Memory + 50V DC

Curve 1 – 4V DC

325V DC

DC Bus Memory

342V DC

375V DC

> 342V DC

Memory + 33V DC

480

< 650V DC

Memory + 100V DC

Curve 1 – 8V DC

650V DC

DC Bus Memory

685V DC

750V DC

> 685V DC

Memory + 65V DC

600

< 813V DC

Memory + 125V DC

Curve 1 – 10V DC

813V DC

DC Bus Memory

856V DC

937V DC

> 856V DC

Memory + 81V DC

600/690V
PowerFlex 700
Frames 5 & 6 Only

< 933V DC

Memory + 143V DC

Curve 1 – 11V DC

933V DC

DC Bus Memory

983V DC

1076V DC

> 983V DC

Memory + 93V DC

Advertising