Power loss, Pet power loss, Terms – Rockwell Automation 20B PowerFlex 70, PowerFlex 700 Reference Manual User Manual
Page 128

PET
128
Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013
PET
Pulse Elimination Technique – See
Power Loss
Some processes or applications cannot tolerate drive output interruptions caused
by momentary power outages. When AC input line power is interrupted to the
drive, user programming can determine the drive’s reaction.
Terms
The following is a definition of terms. Some of these values are drive parameters
and some are not. The description of how these operate is explained below
Table 14 PF70 Bus Levels
Term
Definition
Vbus
The instantaneous DC bus voltage.
Vmem
The average DC bus voltage. A measure of the “nominal” bus voltage determined by heavily filtering bus
voltage. Just after the pre-charge relay is closed during the initial power-up bus pre-charge, bus memory
is set equal to bus voltage. Thereafter it is updated by ramping at a very slow rate toward Vbus. The filtered
value ramps at 2.4V DC per minute (for a 480VAC drive). An increase in Vmem is blocked during
deceleration to prevent a false high value due to the bus being pumped up by regeneration. Any change to
Vmem is blocked during inertia ride through.
Vslew
The rate of change of Vmem in volts per minute.
Vrecover
The threshold for recovery from power loss.
Vtrigger
The threshold to detect power loss.
PowerFlex 700
The level is adjustable. The default is the value in the PF700 Bus Level table. If “Pwr Loss Lvl” is selected as
an input function AND energized, Vtrigger is set to Vmem minus [Power Loss Level].
Vopen is normally 60V DC below Vtrigger (in a 480VAC drive). Both Vopen and Vtrigger are limited to a
minimum of Vmin. This is only a factor if [Power Loss Level] is set to a large value.
PowerFlex 70
This is a fixed value.
WARNING:
When using a value of Parameter #186 [Power Loss Level] larger than default, the customer must provide a
minimum line impedance to limit inrush current when the power line recovers. The input impedance
should be equal or greater than the equivalent of a 5% transformer with a VA rating 5 times the drive’s
input VA rating.
Vinertia
The software regulation reference for Vbus during inertia ride through.
Vclose
The threshold to close the pre-charge contactor.
Vopen
The threshold to open the pre-charge contactor.
Vmin
The minimum value of Vopen.
Voff
The bus voltage below which the switching power supply falls out of regulation.
Class
200/240 VAC
400/480 VAC
600/690 VAC
Vslew
1.2V DC
2.4V DC
3.0V DC
Vrecover
Vmem – 30V
Vmem – 60V
Vmem – 75V
Vclose
Vmem – 60V
Vmem – 120V
Vmem – 150V
Vtrigger1
Vmem – 60V
Vmem – 120V
Vmem – 150V
Vtrigger2
Vmem – 90V
Vmem – 180V
Vmem – 225V
Vopen
Vmem – 90V
Vmem – 180V
Vmem – 225V
Vmin
204V DC
407V DC
509V DC
Voff 3
?
300V DC
?