Power loss, Pet power loss, Terms – Rockwell Automation 20B PowerFlex 70, PowerFlex 700 Reference Manual User Manual

Page 128

Advertising
background image

PET

128

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

PET

Pulse Elimination Technique – See

Reflected Wave on page 149

.

Power Loss

Some processes or applications cannot tolerate drive output interruptions caused
by momentary power outages. When AC input line power is interrupted to the
drive, user programming can determine the drive’s reaction.

Terms

The following is a definition of terms. Some of these values are drive parameters
and some are not. The description of how these operate is explained below

Table 14 PF70 Bus Levels

Term

Definition

Vbus

The instantaneous DC bus voltage.

Vmem

The average DC bus voltage. A measure of the “nominal” bus voltage determined by heavily filtering bus
voltage. Just after the pre-charge relay is closed during the initial power-up bus pre-charge, bus memory
is set equal to bus voltage. Thereafter it is updated by ramping at a very slow rate toward Vbus. The filtered
value ramps at 2.4V DC per minute (for a 480VAC drive). An increase in Vmem is blocked during
deceleration to prevent a false high value due to the bus being pumped up by regeneration. Any change to
Vmem is blocked during inertia ride through.

Vslew

The rate of change of Vmem in volts per minute.

Vrecover

The threshold for recovery from power loss.

Vtrigger

The threshold to detect power loss.

PowerFlex 700
The level is adjustable. The default is the value in the PF700 Bus Level table. If “Pwr Loss Lvl” is selected as
an input function AND energized, Vtrigger is set to Vmem minus [Power Loss Level].
Vopen is normally 60V DC below Vtrigger (in a 480VAC drive). Both Vopen and Vtrigger are limited to a
minimum of Vmin. This is only a factor if [Power Loss Level] is set to a large value.

PowerFlex 70
This is a fixed value.
WARNING:
When using a value of Parameter #186 [Power Loss Level] larger than default, the customer must provide a
minimum line impedance to limit inrush current when the power line recovers. The input impedance
should be equal or greater than the equivalent of a 5% transformer with a VA rating 5 times the drive’s
input VA rating.

Vinertia

The software regulation reference for Vbus during inertia ride through.

Vclose

The threshold to close the pre-charge contactor.

Vopen

The threshold to open the pre-charge contactor.

Vmin

The minimum value of Vopen.

Voff

The bus voltage below which the switching power supply falls out of regulation.

Class

200/240 VAC

400/480 VAC

600/690 VAC

Vslew

1.2V DC

2.4V DC

3.0V DC

Vrecover

Vmem – 30V

Vmem – 60V

Vmem – 75V

Vclose

Vmem – 60V

Vmem – 120V

Vmem – 150V

Vtrigger1

Vmem – 60V

Vmem – 120V

Vmem – 150V

Vtrigger2

Vmem – 90V

Vmem – 180V

Vmem – 225V

Vopen

Vmem – 90V

Vmem – 180V

Vmem – 225V

Vmin

204V DC

407V DC

509V DC

Voff 3

?

300V DC

?

Advertising
This manual is related to the following products: