Speed Units

176

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

Speed Units

[Speed Units] selects the units to be used for all speed related

parameters. The options for [Speed Units] are:

“Hz” – converts status parameters only to Hz.

“RPM” – converts status parameters only to RPM.

“Convert Hz” - converts all speed based parameters to Hz, and changes the
value proportionately (i.e. 1800 RPM = 60 Hz).

“Convert RPM” - converts all speed based parameters to RPM, and changes
the value proportionately.

Start Inhibits

The [Start Inhibits] parameter indicates the inverted state of all start permissive
conditions. If the bit is on (HI or 1), the corresponding permissive requirement
has not been met and the drive is inhibited from starting. It will be updated
continually, not only when a start attempt is made. See also

Start Permissives on

page 176

.

Start Permissives

Start permissives are conditions required to permit the drive to start in any mode
– run, jog, auto-tune, etc. When all permissive conditions are met the drive is
considered

ready to start. The ready condition is available as the drive ready

status.

Permissive Conditions

1.

No faults can be active.

2.

No type2 alarms can be active.

3.

The TB Enable input (if configured) must be closed.

4.

The DC bus precharge logic must indicate it is a start permissive.

5.

All Stop inputs must be negated (See special Digital Inputs Stops
Configuration issues below).

6.

No configuration changes (parameters being modified) can be in-progress.

If all permissive conditions are met, a valid start, run or jog command will start
the drive. The status of all inhibit conditions, except for item

6

above, are

reflected in the output parameter Start Inhibits. The configuration change
condition is a transient (short-term) condition and not directly user controlled. It
is therefore not reflected in the Start Inhibits parameter.

Note that the Start Inhibits conditions do not include any of the functionality