Start-Up

182

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

Figure 44 PowerFlex 70 & 700 Standard Control Option Startup (4)

4-6

StartUp
4. Speed Limits

Disable reverse
operation?

Yes
<No>

Basic Start Up (Speed Limits)

StartUp
4. Speed Limits

This section
defines min/max
speeds, and
direction method

4-0

Enter

4-1

Yes

StartUp
4. Speed Limits

Enter choice for
Direction Method

<Fwd/Rev Command>
+/- Speed Ref

No

Enter

4-2

4-5

StartUp
4. Speed Limits

Enter value for

Maximum Speed

+60.00 Hz
xxx.xx <> yyy.yy

Enter

4-4

4-3

StartUp
4. Speed Limits

Maximum Freq and
Overspeed Limit
will be changed
to support your
Maximum Speed.

Yes

Reject

StartUp
4. Speed Limits

Enter value for

Minimum Speed

+5.78 Hz
xxx.xx <> yyy.yy

No

Go to 0-1 (5)

Enter

Enter

Backup

Backup

Backup

StartUp
4. Speed Limits

Rejecting this
change will
prevent starting

Accept
Reject

MaxFreq = MaxSpd

+ OS Limit

MaxSpd + OS
Lmt > 400Hz?

Accept

No

Yes

MaxFreq = 400Hz

OS Limit =

MaxFreq - MaxSpd

MaxSpd + OSL

> MaxFreq?