Start-Up

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

191

Figure 53 PowerFlex 700 Vector Control Option Startup (5)

Start-Up
5. Speed Control
Enter value for
Speed Ref A Hi
60.0 Hz
x.x < y.y

Start-Up
5. Speed Control
Enter value for
Speed Ref A Lo
0.0 Hz
x.x < y.y

Start-Up
5. Speed Control
Choose source
of Reference:
<1.Analog Input>
2.Preset Speed 1
3.Digital Inputs
4.Comm Adapter
5.Local HIM
6.Remote HIM
7.MOP

Flux Vector Start Up (Speed/Torque Control)

Start-Up
5. Speed Control
This section
selects the
speed/torque
control source.

5-0

5-1

5-21

5-24

Start-Up
5. Speed Control
Enter choice for
Signal Type
<Voltage>
Current

No-If AIn 1 Hi/Lo

value out of range,

set to min of Signal

type selected

Start-Up
5. Speed Control
Enter value for
Analog In 1 Hi
10.0 V
x.xxxx < y.yyyy

Start-Up
5. Speed Control
Enter value for
Analog In 1 Lo
0.0 V
x.xxxx < y.yyyy

5-18

5-20

5-23

Go to 0-1

(6. Strt/Stop/I/O)

Start-Up
5. Speed Control
Save MOP speed
at power down ?
<Yes>
No

PF70 Start-Up
5. Speed Control
Enter value for
MOP Rate
5.0 Hz
xx.x < yy.y

Upon "Enter", write to

bit '0' of param #194

(Save MOP Ref)

5-15

5-17

Set #90 to

Analog Input 1

Start-Up
5. Speed Control
Enter choice for
Input Signal
<Analog Input 1>
Analog Input 2

5-13

Analog Input

Start-Up
5. Speed Control
Enter value for
Speed Ref A Hi
60.0 Hz
x.x < y.y

Start-Up
5. Speed Control
Enter value for
Speed Ref A Lo
0.0 Hz
x.x < y.y

5-28

5-31

Start-Up
5. Speed Control
Enter choice for
Signal Type
<Voltage>
Current

No-If AIn 2 Hi/Lo

value out of range,

set to min of Signal

type selected.

Start-Up
5. Speed Control
Enter value for
Analog In 2 Hi
10.0 V
x.xxxx < y.yyyy

Start-Up
5. Speed Control
Enter value for
Analog In 2 Lo
0.0 V
x.xxxx < y.yyyy

5-25

5-27

5-30

Set #90 to

Analog Input 2

Start-Up
Comm Adapter
Make a selection
<Port 5-internal>
Port 2-common
Port 3-external
Port 4-external

5-2

Start-Up
Remote HIM
Make a selection
<Port 2 (common)>
Port 3
Port 4

5-3

Start-Up
5. Speed Control
Select a Preset
Speed:
<1.Preset Speed 1>
2.Preset Speed 2
3.Preset Speed 3
4.Preset Speed 4
5.Preset Speed 5
6.Preset Speed 6
7.Preset Speed 7
8.Done

Start-Up
5. Speed Control
Enter value for
Preset Speed 1
5.0 Hz
xxx.x < yyy.y

5-12

5-4

Start-Up
5. Speed Control
Enter value for
Preset Speed 2
10.0 Hz
xxx.x < yyy.y

5-5

Start-Up
5. Speed Control
Enter value for
Preset Speed 3
15.0 Hz
xxx.x < yyy.y

5-6

Start-Up
5. Speed Control
Enter value for
Preset Speed 4
20.0 Hz
xxx.x < yyy.y

5-7

Start-Up
5. Speed Control
Enter value for
Preset Speed 5
25.0 Hz
xxx.x < yyy.y

5-8

Start-Up
5. Speed Control
Enter value for
Preset Speed 6
30.0 Hz
xxx.x < yyy.y

5-9

Start-Up
5. Speed Control
Enter value for
Preset Speed 7
35.0 Hz
xxx.x < yyy.y

5-10

Remote

HIM -write

to #90 (Ref

A Sel)

selection

Preset

Speed - Set

param #90

(Ref A Sel)

to '11'

Go to 0-1 (6.Strt/

Stop/I/O)

Start-Up
5. Speed Control
Digital Inputs
5 & 6 will be
set to MOP Inc &
MOP Dec.

5-14

Start-Up
5. Speed Control
Save MOP speed
at Stop ?
<Yes>
No

5-16

Upon "Enter", write to

bit '1' of param #194

(Save MOP Ref)

Enter

Done

Preset

Speed 1

Preset

Speed 2

Preset

Speed 3

Preset

Speed 4

Preset

Speed 5

Preset

Speed 6

Preset

Speed 7

Go to 0-1 (6. Strt/

Stop/I/O)

Local HIM- Port 1-

Set param #90

(Ref A Sel) to '18'

MOP - Set

Param #90
(Ref A Sel)

to '9'

Enter/

Backup

5-22

5-29

5-19

5-26

Enter

Start-Up
5. Speed Control
Note: Factory
default settings
provide preset
speed operation
from the digital
inputs.

Comm Adapter -

write to #90 (Ref A

Sel) selection

5-11

Note :
- For V/Hz mode, the MOP option in 5-1 is NOT displayed, screens 5-14
thru 5-17 and 5-18 thru 5-31 are also NOT displayed.

Start-Up
5. Speed Control
Verify high/low
speeds with
high/low analog
signals.

5-32

Enter

V/Hz

Mode?

Set bit 0 of #320 to '0'

(for Volts) & '1' (for Amps)

Set bit 1 of #320 to '0'

(for Volts) & '1' (for Amps)

Yes

V/Hz

Mode?

Start-Up
5. Speed Control
Configure other
Spd References?
<Yes>
No

Go to 5-1

5-33

No

Yes

Start-Up
5. Speed Control
The next two
steps scale a
low speed with
a low analog
value.

Start-Up
5. Speed Control
The next two
steps scale a
high speed to
a high analog
value.

Start-Up
5. Speed Control
The next two
steps scale a
low speed with
a low analog
value.

Start-Up
5. Speed Control
The next two
steps scale a
high speed to
a high analog
value.

Flux

Vector

Mode?

No

Yes

Start-Up
C. Anlg Inputs
Enter choice for
Reference::
<Speed>
Torque

Speed

Go to 6-49

Torque

5-34

Note:
- Only Analog and Local HIM
are displayed in 5-1 for Basic
mode.

Digital
Inputs

Start-Up

5. Speed Control

Enter value for
Preset Speed 1
5.0 Hz
xxx.x < yyy.y

Set params: #90 (Ref A

Sel) to Anlg In 1; #93 (Ref

B Sel) to Preset Spd 1;
#364-66 (Digital In 4-6)

to Speed Sel 1, 2, 3.

5-35