Rockwell Automation 20B PowerFlex 70, PowerFlex 700 Reference Manual User Manual

Page 188

Advertising
background image

Start-Up

188

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

Figure 50 PowerFlex 700 Vector Control Option Startup (2)

Start-Up
2. Motr Dat/Ramp

Enter value for

Motor NP Power

123.4 kW
xxx.x <> yyy.y

Start-Up
2. Motr Dat/Ramp

Enter value for

Motor NP Volts

123.4 Volt
xxx.x <> yyy.y

Start-Up
2. Motr Dat/Ramp

Enter value for

Motor NP FLA

+456.78 Amps
xxx.xx <> yyy.yy

Start-Up
2. Motr Dat/Ramp

Enter value for

Motor NP RPM

+456 RPM
xxx <> yyy

Start-Up
2. Motr Dat/Ramp

Enter value for

Motor NP Hertz

60.0 Hz
x.x <> y.y

Start-Up
2. Motr Dat/Ramp

Enter choice for
Power Units

<HP>

Killowatt

Go to 0-1 (3. Motor

Tests)

Start-Up
2. Motr Dat/Ramp

Enter value for

Accel Time 1

6.0 Secs
0.0 < 60.0 secs

Start-Up
2. Motr Dat/Ramp

Enter value for

Decel Time 1

6.0 Secs
0.0 < 60.0 secs

Start-Up
2. Motr Dat/Ramp

Enter value for

S Curve %

0 %
0 < 100 %

Start-Up
2. Motr Dat/Ramp

Use motor name-
plate data and
required ramp
times for the
following steps.

Flux Vector Start Up (Motor Dat/Ramp)

2-0

Enter

2-1

2-2

Enter

Enter

2-3

Enter

2-4

Enter

2-5

2-6

Enter

2-11

Enter

2-12

2-13

Enter

Enter

Start-Up
2. Motr Dat/Ramp

Enter Stop Mode:

1.Coast
<2.Ramp>
3.Ramp to Hold
4.DC Brake

2-7

Enter

Use formula:

Poles= 120 * NP Hz

NP RPM

as Motor Poles

parameter value.

Stop Mode A =

"DC Brake" or

"Ramp to Hold"?

Start-Up
2. Motr Dat/Ramp

Enter value for

DC Brake Level

1.0 Amps
0.0 < 30.0 Amps

2-8

Yes

Start-Up
2. Motr Dat/Ramp

Enter value for

DC BrakeTime

1.0 Secs
0.0 < 90.0 Secs

2-9

Enter

No

Start-Up
2. Motr Dat/Ramp

Enter choice for
DB Resistor type

<None>
Internal
External

2-10

Enter

Enter

Backup

Note

: Depending on selection, set parameter

#161 (Bus Reg Mode A):
None - Bus Reg Mode A = Adj Freq.
Intenal - Bus Reg Mode A = Both, DB 1st.
External - Bus Reg Mode A = Both, DB 1st.

Stop Mode A =

"DC Brake"?

Yes

No

Start-Up
2. Motr Dat/Ramp

Enter value for

Motor Poles

12
xx <> yy

2-14

Note:

- For V/Hz mode, only states 2-0 thru 2-6 & 2-14 are displayed.
- For V/Hz mode, configure Stop Mode A as Coast to Stop.
- Going from state 2-7 to 2-10 directly sets the DC Brake Level/Time
parameters to their default value.

Note

: If Stop Mode A = COAST, then

skip 2-10.

Note

: If Stop Mode A = COAST, then

skip 2-12. If in Quick/Basic mode, then
exit Motor Data/Ramp.

B

= Basic mode

B

B

B

B

B

B

B

Note

: Default should be

NONE

.

B

B

Advertising
This manual is related to the following products: