Rockwell Automation 20B PowerFlex 70, PowerFlex 700 Reference Manual User Manual

Page 129

Advertising
background image

Power Loss

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

129

Table 15 PF700 Bus Levels

Note 1:Vtrigger is adjustable, these are the standard values.

Class

200/240V AC

400/480V AC

600/690V AC

Vslew

1.2V DC

2.4V DC

3.0V DC

Vrecover

Vmem – 30V

Vmem – 60V

Vmem – 75V

Vclose

Vmem – 60V

Vmem – 120V

Vmem – 150V

Vtrigger1,2

Vmem – 60V

Vmem – 120V

Vmem – 150V

Vtrigger1,3

Vmem – 90V

Vmem – 180V

Vmem – 225V

Vopen

Vmem – 90V

Vmem – 180V

Vmem – 225V

Vopen4

153V DC

305V DC

382V DC

Vmin

153V DC

305V DC

382V DC

Voff 5

200V DC

350

400

450

400

450

500

550

600

650

700

AC Input Volts

DC Bus Volts

Recover
Close
Trigger
Open

350

400

450

400

450

500

550

600

650

700

AC Input Volts

DC Bus Volts

Recover
Close
Trigger
Open

Line Loss Mode = Decel

Line Loss Mode = Coast

350

400

450

300

350

400

450

500

550

600

650

700

AC Input Volts

DC Bus Volts

Recover
Close
Trigger
Open

350

400

450

300

350

400

450

500

550

600

650

700

AC Input Volts

DC Bus Volts

Recover
Close
Trigger
Open

Line Loss Mode = Coast

Line Loss Mode = Decel

350

400

450

300

350

400

450

500

550

600

650

700

AC Input Volts

DC Bus Volts

Recover
Close
Trigger
Open

Line Loss Mode = Continue