Start-Up

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

181

Figure 43 PowerFlex 70 & 700 Standard Control Option Startup (3)

Basic Start Up (Motor Tests)

Startup
3. Motor Tests

This section
optimizes torque
performance and
tests for proper
direction.

3-0

Go to 0-1 (4)

Startup
B. Directn Test

Press Jog or Start
to begin.

Startup
B. Directn Test

Is direction of
motor forward?

<Yes>
No

Startup
B. Directn Test

Press Enter.
Then power down
and swap 2 output
wires to motor.

Start

Startup
A. AutoTune

Make a selectioon

<Rotate Tune>
Static Tune

Startup
B. Directn Test

Test complete.

Startup
A. Auto Tune.

Static Tune will
energize motor
with no shaft
rotation. Press
Start to begin.

Startup
A. Auto Tune

Rotate Tune will
energize motor,
then cause shaft
rotation. Press
Start to begin.

Startup
A. Auto Tune

Test complete.

Startup
A. Auto Tune

Executing test.
Please wait....

Rotate/Static

Tune complete

(stops drive)

Static

Tune

Rotate

Tune

Direction

Test

3-3

Done

No

(stops drive)

Yes

(stops drive)

Start

Enter/

Backup

Startup
3. Motor Tests

Test aborted due
to user stop.
Clear fault to
continue.

3-8

3-9

3-10

3-11

3-6

3-7

3-5

3-12

3-4

Startup
3. Motor Tests

Test aborted!
Clear the fault.
Check motor data
settings. Verify
load is removed.

3-13

Fault

Fault Clear

Startup
3. Motor Tests

Complete these
steps in order:

<A. Auto Tune>
B. Directn Test
C. Done

3-1

Auto Tune

Enter/

Backup

Enter/

Backup

Startup
A. AutoTune

Rotate Tune only
with no load and
low friction.
Static Tune when
load or friction
are present.

Enter

3-2

Enter

Start

Stop or Esc

(stops drive)