Rockwell Automation 20B PowerFlex 70, PowerFlex 700 Reference Manual User Manual

Page 25

Advertising
background image

Analog Inputs

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

25

Configuration #5:

[Anlg In Config], bit 0 = “0” (Voltage)

[Speed Ref A Sel] = “Analog In 1”

[Speed Ref A Hi] = 60 Hz

[Speed Ref A Lo] = 0 Hz

[Analog In 1 Hi] = 5V

[Analog In 1 Lo] = 0V

This configuration is used when the input signal is 0-5 volts. Here, minimum
input (0 Volts) represents 0 Hz and maximum input (5 Volts) represents 60 Hz.
This allows full scale operation from a 0-5 volt source.

Analog Scaling
[Speed Reference A Sel] = “Analog In 1”
[Analog In 1 Hi]
10V

[Speed Ref A Hi]
0 Hz

[Analog In 1 Lo]
0V

[Speed Ref A Lo]
60 Hz

Analog Scaling
[Speed Reference A Sel] = “Analog In 1”
[Analog In 1 Hi]
5V

[Speed Ref A Hi]
60 Hz

[Analog In 1 Lo]
0V

[Speed Ref A Lo]
0Hz

2

4

6

8

10

6

0

12

18

Output Hertz

Input Volts

24

30

36

42

48

54

60

1

2

3

4

5

6

6

0

12

18

Output Hertz

Input Volts

24

30

36

42

48

54

60