Digital Inputs

72

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

PowerFlex 70 Digital Input Selection

The available functions are defined in

Table 9

.

Table 9 Digital Input Function List

INPUT

S &

OUTP

UTS

(File

J)

D

igital Inputs

361

362

363

364

365

366

[Digital In1 Sel]

[Digital In2 Sel]
[Digital In3 Sel]
[Digital In4 Sel]
[Digital In5 Sel]
[Digital In6 Sel]

Selects the function for the digital inputs.

(1)

When [Digital Inx Sel] is set to option 2 “Clear

Faults” the Stop button cannot be used to clear a
fault condition.

(2)

Typical 3-Wire Inputs.
Requires that only 3-wire functions are chosen.
Including 2-wire selections will cause a type 2
alarm.

(3)

Typical 2-Wire Inputs.
Requires that only 2-wire functions are chosen.
Including 3-wire selections will cause a type 2
alarm.

(4)

Speed Select Inputs.

To access Preset Speed 1, set [Speed Ref A Sel]
or [Speed Ref B Sel] to “Preset Speed 1”.
Type 2 Alarms
Some digital input programming may cause
conflicts that will result in a Type 2 alarm. Example:
[Digital In1 Sel] set to 5 “Start” in 3-wire control and
[Digital In2 Sel] set to 7 “Run” in 2-wire.
Refer to Alarm Descriptions in the User Manual for
information on resolving this type of conflict.

(5)

Auto/Manual - Refer to User Manual for details.

(6)

Opening an “Enable” input will cause the motor to
coast-to-stop, ignoring any programmed Stop
modes.

(7)

A “Dig In ConflictB” alarm will occur if a “Start”
input is programmed without a “Stop” input.

Default:

Default:
Default:
Default:
Default:
Default:

Options:

4

5
18
15
16
17

0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

“Stop – CF”
(CF = Clear Fault)
“Start”
“Auto/ Manual”
“Speed Sel 1”
“Speed Sel 2”
“Speed Sel 3”

“Not Used”
“Enable”

(6)

“Clear Faults”

(1)

“Aux Fault”
“Stop – CF”

(2)

“Start”

(2)(7)

“Fwd/ Reverse”

(2)

“Run”

(3)

“Run Forward”

(3)

“Run Reverse”

(3)

“Jog”

(2)

“Jog Forward”
“Jog Reverse”
“Stop Mode B”
“Bus Reg Md B”
“Speed Sel 1”

(4)

“Speed Sel 2”

(4)

“Speed Sel 3”

(4)

“Auto/ Manual”

(5)

“Local”
“Acc2 & Dec2”
“Accel 2”
“Decel 2”
“MOP Inc”
“MOP Dec”
“Excl Link”
“PI Enable”
“PI Hold”
“PI Reset”

100

156
162

096

140

194

380
384
388
124

Input Function Name

Purpose

Stop - CF

Stop drive
Clear Faults (open to closed transition)

Run Forward

Run in forward direction (2-wire start mode)

Run Reverse

Run in reverse direction (2-wire start mode)

Run

Run in current direction (2-wire start mode)

Start

Start drive (3-wire start mode)

Forward/Reverse

Set drive direction (3-wire mode only)

Jog

Jog drive

Jog Forward

Jog in forward direction

Jog Reverse

Jog in reverse direction

Speed Select 3
Speed Select 2
Speed Select 1

Select which Speed reference the drive uses.

Auto/Manual

Allows terminal block to assume complete control of Speed Reference.

3

2

1

Auto Reference Source

0
0
0
0
1
1
1
1

0
0
1
1
0
0
1
1

0
1
0
1
0
1
0
1

Reference A
Reference B
Preset Speed 2
Preset Speed 3
Preset Speed 4
Preset Speed 5
Preset Speed 6
Preset Speed 7