Rockwell Automation 20B PowerFlex 70, PowerFlex 700 Reference Manual User Manual

Page 64

Advertising
background image

CE Conformity

64

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

Table 5 PowerFlex 70 – EN61800-3 EMC Compatibility

Table 6 PowerFlex 70 – EN61800-3 First Environment Restricted Distribution

)

Table 7 PowerFlex 700 EN61800-3 EMC Compatibility

(1)

(1) External filters for First Environment installations and increasing motor cable lengths in Second Environment

installations are available. Roxburgh models KMFA (RF3 for UL installations) and MIF or Schaffner FN3258
and FN258 models are recommended. Refer to

Table 8

and http://www.deltron-emcon.com and http://

www.mtecorp.com (USA) or http://www.schaffner.com, respectively.

(2) Two turns of the blue comm option cable through a Ferrite Core (Frames A, B, C Fair-Rite #2643102002, Frame

D Fair-Rite #2643251002 or equivalent).

(3) Refer to the 1321 Reactor and Isolation Transformer Technical Data publication, 1321-TD001x for 1321-Mxxx

selection information.

Fr

am

e

Drive Description

Second Environment
Restrict Motor Cable
to 40 m (131 ft.)

Internal Filter
Option

External
Filter

(1)

Input
Ferrite

(2)

A

Drive Only

Drive with any Comm Option

Drive with Remote I/O

B

Drive Only

Drive with any Comm Option

Drive with Remote I/O

C

Drive Only

Drive with any Comm Option

Drive with Remote I/O

D

Drive Only

Drive with any Comm Option

Drive with Remote I/O

E

Drive Only

Drive with any Comm Option

Drive with Remote I/O

Fram

e

Drive Description

First Environment Restricted Distribution
Restrict Motor
Cable to:

Internal
Filter Option

External
Filter

(1)

Comm Cable
Ferrite

(2)

Common Mode
Core

(3)

A

Drive Only

40 m (131 ft.)

Drive with any Comm Option

40 m (131 ft.)

Drive with Remote I/O

40 m (131 ft.)

B

Drive Only

12 m (40 ft.)

Drive with any Comm Option

12 m (40 ft.)

Drive with Remote I/O

12 m (40 ft.)

C

Drive Only

12 m (40 ft.)

Drive with any Comm Option

12 m (40 ft.)

Drive with Remote I/O

12 m (40 ft.)

D

Drive Only

12 m (40 ft.)

Drive with any Comm Option

12 m (40 ft.)

Drive with Remote I/O

12 m (40 ft.)

E

Drive Only

30 m (98 ft.)

Drive with any Comm Option

30 m (98 ft.)

Drive with Remote I/O

30 m (98 ft.)

Fram

e

Second Environment

Restrict Motor Cable to 30 m (98 ft.)

First Environment Restricted Distribution

Restrict Motor Cable to 150 m (492 ft.)

Any Drive and Option

Any Drive and Option

External Filter Required