Start-Up

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

177

Start-Up

Start-Up Routines

PowerFlex drives offer a variety of Start Up routines to help the user commission
the drive in the easiest manner and the quickest possible time. PowerFlex 70
Drives have the S.M.A.R.T Start routine and a Basic assisted routine for more
complex setups. PowerFlex 700 drives have both of the above plus an advanced
startup routine.

S.M.A.R.T. Start

During a Start Up, the majority of applications require changes to only a few
parameters. The LCD HIM on a PowerFlex 70 drive offers S.M.A.R.T. start,
which displays the most commonly changed parameters. With these parameters,
you can set the following functions:

S - Start Mode and Stop Mode
M - Minimum and Maximum Speed
A - Accel Time 1 and Decel Time 1
R - Reference Source
T - Thermal Motor Overload

To run a S.M.A.R.T. start routine:

Basic Start Up

The Basic Start Up routine leads the user through the necessary information in a
simple question and answer format. The user can make the choice to execute or
skip any section of the routine. Below is a complete flow chart of the routine.

Step

Key(s)

Example LCD Displays

1. Press ALT and then Esc (S.M.A.R.T). The S.M.A.R.T.

start screen appears.

2. View and change parameter values as desired. For

HIM information, see Appendix B.

3. Press ALT and then Sel (Exit) to exit the S.M.A.R.T.

start.

ALT

ALT

Esc

Sel

S.M.A.R.T. List
Start Mode
Stop Mode
Minimum Speed

Advertising