Rockwell Automation 20B PowerFlex 70, PowerFlex 700 Reference Manual User Manual

Page 187

Advertising
background image

Start-Up

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

187

Figure 49 PowerFlex 700 Vector Control Option Startup (1)

Start-Up
V/Hz
Enter value for
Break Voltage
10.0 Hz
x.x < y.y

Start-Up
V/Hz
Enter value for
Max Voltage
10.0 V
x.x < y.y

Start-Up
1. Motor Control
Make a selection
<1.SVC>
2.V/Hz
3.Flux Vector
4.More info

Flux Vector Start Up (Motor Control Select)

Start-Up
1. Motor Control
This section
selects the type
of Motor Control
the drive will
use.

1-0

1-1

1-6

Start-Up
V/Hz
Enter value for
Start Boost
10.0 V
x.xxxx < y.yyyy

Start-Up
V/Hz
Enter value for
Break Frequency
10.0 Hz
x.xxxx < y.yyyy

1-3

1-5

Go to 0-1

2. Motr Dat/Ramp

1-9

Start-Up
V/Hz
Enter value for
Run Boost
10V
xx.x < yy.y

1-8

1-4

1-10

Speed path-
Set #88 to 1

Start-Up
Flux Vector
Enter value for
Encoder PPR
1024

1-11

Start-Up
V/Hz
Select a V/Hz
control option:
<1.V/Hz-Fan/Pump>
2.V/Hz-Cust/Std.
3.More info

Start-Up
Flux V ector
Control selected
is FOC Speed
Regulate.

Enable

Set #80=1

V/Hz

Custom/Std.

Start-Up
V\Hz
Control selected
is Standard V/Hz

Standard-

set params #54

& 69-72 to

default values

Start-Up
V/Hz
Control selected
is Fan/Pump
with Slip Comp

Start-Up
V/Hz
Control selected
is Fan/Pump
no Slip Comp

1-12

1-13

1-14

1-15

1-16

1-17

1-18

1-19

Start-Up
Flux Vector
NOTE! An Encoder
is required for
the Flux Vector
Control option.

Start-Up
V/Hz
Control selected
is V/Hz/Custom
with Slip Comp.

1-20

Start-Up
Flux Vector
Control selected
is Torque/FOC
Torque Regulate

1-7

Trq

Regulate

Set #88

= 2

1-21

Start-Up
Flux Vector
Select Torque
Regulate option:
<1.Torque Regul.>
2.Min Torque/Spd
3.Max Torque/Spd
4.Sum Torque/Spd
5.Absolute

1-22

Start-Up
Flux Vector
Enter choice of
Speed Units
<Hz>
RPM

1-2

1-23

Start-Up
Flux Vector
Control selected
is Torque/FOC
Min Torque/Speed

Start-Up
Flux Vector
Control selected
is Torque/FOC
Max Torque/Speed

1-24

1-25

Min Torque/

Speed -

Set #88 =3

Max

Trq/Speed -

Set #88 = 4

Start-Up
Flux Vector
Control selected
is Torque/FOC
Sum Torque/Speed

Sum Trq/Speed-

Set #88 = 5

Start-Up
Flux Vector
Control selected
is Torque/FOC
Absolute

Absolute-

Set #88

= 6

1-26

Set #80 to

selection made

Start-Up
1.Motor Control
Use SVC
for applications
requiring speed
regulation.
Use V/Hz control
for Fan/Pump and
other V/Hz
applications.
Use Flux Vector
for applications
requiring Torque
control or tight
speed regulation.

Frequency

More

info

Start-Up
SVC
Enter choice of
Speed Units
<Hz>
RPM

SVC- Set

#53= 0

Flux

Vector

Start-Up
Flux Vector
Enter choice of
Regulation
<Speed>
Torque

Start-Up
SVC
Control selected
is SVC with
no Slip Comp

Start-Up
SVC
Control selected
is SVC with
Slip Comp

Start-Up
V/Hz
Enter choice for
Slip Comp
<Enable>
Disable

Start-Up
V/Hz
Enter choice for
Slip Comp
<Enable>
Disable

Fan/Pump-Set #53=3

Disable

Set #80=0

Enable

Set #80=1

Torque path

Start-Up
SVC
Enter choice for
Slip Comp
<Enable>
Disable

Disable

Set #80=0

1-27

1-28

1-29

1-30

1-31

1-32

Start-Up
V/Hz
Control selected
is V/Hz/Custom
no Slip Comp.

Start-Up
V/Hz
The Fan/Pump
option selects a
predefined V/Hz
curve.
The Custom/Std.
option allows
you to define a
V/Hz curve or
select a default
V/Hz curve.

More

info

B = Basic mode

B

B

B

B

B

B

B

B

Start-Up
V/Hz
Define Custom
V/Hz curve?
<Yes>

No

Yes

Advertising