Analog Inputs

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

23

Configuration #2:

[Anlg In Config], bit 0 = “0” (Voltage)

[Speed Ref A Sel] = “Analog In 1”

[Speed Ref A Hi] = 30 Hz

[Speed Ref A Lo] = 0 Hz

[Analog In 1 Hi] = 10V

[Analog In 1 Lo] = 0V

This is an application that only requires 30 Hz as a maximum output frequency,
but is still configured for full 10 volt input. The result is that the resolution of the
input has been doubled, providing only 3 Hz change per input volt
(Configuration #1 is 6 Hz/Volt).

Analog Scaling
[Speed Reference A Sel] = “Analog In 1”
[Analog In 1 Hi]
10V

[Speed Ref A Hi]
60 Hz

[Analog In 1 Lo]
0V

[Speed Ref A Lo]
0 Hz

Analog Scaling
[Speed Reference A Sel] = “Analog In 1”
[Analog In 1 Hi]
10V

[Speed Ref A Hi]
30 Hz

[Analog In 1 Lo]
0V

[Speed Ref A Lo]
0 Hz

2

4

6

8

10

12

6

0

12

18

Output Hertz

Input Volts

24

30

36

42

48

54

60

2

4

6

8

10

12

6

0

12

18

Output Hertz

Input Volts

24

30

36

42

48

54

60