Dc bus voltage / memory, Decel time, Dc bus voltage / memory decel time – Rockwell Automation 20B PowerFlex 70, PowerFlex 700 Reference Manual User Manual

Page 69

Advertising
background image

DC Bus Voltage / Memory

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

69

Even if non-consecutive Datalinks are used (in the next example, Datalinks A1
and B2 would not be used), data is still returned in the same way.

32-bit data is stored in binary as follows:

Example

Parameter 242 - [Power Up Marker] = 88.4541 hours
MSW = 13

decimal

= 1101

binary

= 2

16

+ 2

18

+ 2

19

= 851968

LSW = 32573
851968 + 32573 = 884541

DC Bus Voltage / Memory

[DC Bus Voltage] is a measurement of the instantaneous value. [DC Bus
Memory] is a heavily filtered value or “nominal” bus voltage. Just after the
pre-charge relay is closed during initial power-up bus pre-charge, bus memory is
set equal to bus voltage. Thereafter it is updated by ramping at a very slow rate
toward Vbus. The filtered value ramps at approximately 2.4V DC per minute
(for a 480V AC drive).

Bus memory is used as the base line to sense a power loss condition. If the drive
enters a power loss state, the bus memory will also be used for recovery (i.e.
pre-charge control or inertia ride through upon return of the power source) upon
return of the power source. Update of the bus memory is blocked during
deceleration to prevent a false high value caused by a regenerative condition.

Decel Time

[Decel Time 1, 2]

Sets the rate at which the drive ramps down its output frequency after a Stop
command or during a decrease in command frequency (speed change). The rate
established is the result of the programmed Decel Time and the Minimum and
Maximum Frequency, as follows:

Two decel times exist to allow the user to change rates “on the fly” via PLC
command or digital input. The selection is made by programming [Decel Time
1] & [Decel Time 2] and then using one of the digital inputs ([Digital Inx Sel])
programmed as “Decel 2” (see

Table 9

for further information). However, if a

PLC is used, manipulate the bits of the command word as shown below.

Datalink

Most/Least Significant Word

Parameter

Data (decimal)

A2

MSW

242

13

B1

LSW

242

32573

MSW

2

31

through 2

16

LSW

2

15

through 2

0

Maximum Speed

Decel Time

= Decel Rate (Hz/sec)