Torque Performance Modes

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

201

Torque Performance
Modes

[Torque Perf Mode] or [Motor Cntl Sel] (Vector) selects the output mode of the
drive. The choices are:

Custom Volts/Hertz
Used in multi-motor or synchronous motor applications.

Fan/Pump Volts/Hertz
Used for centrifugal fan/pump (variable torque) installations for additional
energy savings.

Sensorless Vector
Used for most general constant torque applications. Provides excellent
starting, acceleration and running torque.

Sensorless Vector w/Economizer
Used in constant torque applications that have significant “idle” time (time
spent at greatly reduced load) to offer additional energy conservation.

The following table shows the performance differences between V/Hz and
Sensorless Vector.

Volts/Hertz

Volts/Hertz operation creates a fixed relationship between output voltage and
output frequency. The relationship can be defined in two ways.

1.

Fan/Pump
When this option is chosen, the relationship is 1/X

2

. Therefore;

for full frequency, full voltage is supplied and for ½1/2 rated frequency,
1/4 voltage is applied, etc. This pattern closely matches the torque
requirement of a variable torque load (centrifugal fan or pump – load
increases as speed increases) and offers the best energy savings for these
applications.

2.

Custom
Custom Volts/Hertz allows a wide variety of patterns using linear segments.
The default configuration is a straight line from zero to rated voltage and
frequency. This is the same volts/hertz ratio that the motor would see if it

Torque Mode

Fan/Pump and
Custom V/Hz with
Slip Comp

SVC with Slip
Comp

SVC with
Feedback

Flux Vector
without
Feedback

Flux Vector with
Feedback

Speed Regulation
(% of base speed)

0.5%

0.5%

0.1%

0.1%

0.001%

Operating Speed Range

40:1

80:1

80:1

120:1

1000:1

Speed Bandwidth

10 rad/sec

20 rad/sec

20 rad/sec

50 rad/sec

250 rad/sec

Maximum Voltage

Maximum
Frequency

Base Voltage

(Nameplate)

Base Frequency

(Nameplate)

Run Boost

Advertising