Digital Inputs

78

Rockwell Automation Publication PFLEX-RM001H-EN-P - June 2013

The table below describes the various reference sources that can be selected
using all three of the Speed Select input functions.

If any of the three Reference Select input functions are not configured, then
the software will still follow the table, but will treat the unconfigured inputs as
if they are permanently open.

As an example, the table below describes what reference selections can be
made if “Speed Select 1” is the only configured input function. This
configuration allows a single input to choose between [Speed Ref A Sel] and
[Speed Ref B Sel].

As another example, describes what reference selections can be made if the
“Speed Select 3” and “Speed Select 2” input functions are configured, but
“Speed Select 1” is not.

Speed Select 3

Speed Select 2

Speed Select 1

Parameter that determines Reference

Open

Open

Open

[Speed Ref A Sel]

Open

Open

Closed

[Speed Ref B Sel]

Open

Closed

Open

[Preset Speed 2]

Open

Closed

Closed

[Preset Speed 3]

Closed

Open

Open

[Preset Speed 4]

Closed

Open

Closed

[Preset Speed 5]

Closed

Closed

Open

[Preset Speed 6]

Closed

Closed

Closed

[Preset Speed 7]

Speed Select 1

Selected Parameter that determines Reference

Open

[Speed Ref A Sel]

Closed

[Speed Ref B Sel]

Speed Select 3

Speed Select 2

Selected Parameter that determines reference

Open

Open

[Speed Ref A Sel]

Open

Closed

[Preset Speed 2]

Closed

Open

[Preset Speed 4]

Closed

Closed

[Preset Speed 6]

Advertising